Powers MM430 2 Valve HiLo User Manual
Page 2
Set Up Procedure
n
You must follow these procedures in order to properly adjust your Hi/
Lo System. You need flow greater than the minimum shown in capac-
ity table across the valve in order to set a maximum temperature.
1. Close the low flow valve on the outlet of the low flow valve.
2. Open the ball valve at the discharge of the high flow valve.
3. Open enough fixtures to meet the minimum flow requirement as
per capacity table.
4. Set valve temperature. Refer to IS-P-LFMM430.
5. Set the PRV as follows for a 15psi differential.
a) Loosen the locknut at the top of the PRV. This must be all the
way out or you will be limiting the range of the adjustment. b)
Adjust the PRV so the outlet pressure gauge (top) reads 15psi
less than the supply pressure gauge (bottom). Turning the
adjustment screw counterclockwise will increase the differential
across the PRV (allowing the PRV to open later).
6. Close the ball valve at the discharge of the high flow valve and
open the low flow side ball valve by rotating the handle fully
counterclockwise.
7. Open enough fixtures to meet the minimum flow requirement as
per capacity table.
8. Set the temperature for the low flow valve. Refer to
IS-P-LFLM490-LFLM490-10.
9. Open the ball valve at the discharge of high flow valve.
10. Open additional fixtures to create a 20psi differential between
supply and outlet pressure gauges.
11. When water is at desired outlet temperature, verify temperature
remains at set point.
2
Supply Pressure Gauge
Outlet Pressure Gauge
Lock Nut
Turn fully CCW
(counterclockwise)
before setting PRV.
Adjustment Screw
CW: Increases outlet pressure and
decreases differential across PRV or
CCW: Decreases outlet pressure and
increases differential across PRV.
Capacity
n
Flow Capacity at 50-50 Mixed Ratio
P r e s s u r e D r o p A c r o s s V a l v e
Model
Min. Flow
C
V
5psi
10psi
20psi
30psi
45psi
60psi
to ASSE 1017
(34 kPa)
(69 kPa)
(138 kPa)
(207 kPa)
(310 kPa)
(414 kPa)
LFMM431HL
0.5 gpm
9.7
22 gpm
31 gpm
43 gpm
53 gpm
65 gpm
75 gpm
1.89 lpm
83 lpm
117 lpm
163 lpm
201 lpm
246 lpm
284 lpm
LFMM432HL
0.5 gpm
13.0
29 gpm
41 gpm
58 gpm
66 gpm
87 gpm
93 gpm
1.89 lpm
110 lpm
155 lpm
220 lpm
250 lpm
329 lpm
352 lpm
LFMM433HL
0.5 gpm
19.8
44 gpm
63 gpm
86 gpm
108 gpm
133 gpm
153 gpm
1.89 lpm
167 lpm
238 lpm
326 lpm
409 lpm
503 lpm
579 lpm
LFMM434HL
0.5 gpm
24.9
56 gpm
79 gpm
111 gpm
136 gpm
167 gpm
193 gpm
1.89 lpm
212 lpm
299 lpm
420 lpm
515 lpm
632 lpm
731 lpm
LFMM435HL
3.0 gpm
27.7
62 gpm
88 gpm
124 gpm
152 gpm
186 gpm
215 gpm
11.0 lpm
235 lpm
333 lpm
469 lpm
575 lpm
704 lpm
814 lpm
12. Gradually start to close fixtures to verify that the temperature
remains constant through the full range of flow.
13. For any problem, refer to Troubleshooting section of the docu-
ment or contact Powers' Technical Support Department at
1.800.669.5430 or [email protected].
1. Flush all piping thoroughly before installing.
2. Make sure all ball valve handles are in "OFF" position.
3. In order to make any temperature adjustment to the valves,
you must open end-of-line fixtures to ensure you have ade-
quate flow across the valve.
Prior to Installation
n
4. Use a thermometer at the showerhead or install an in-line
thermometer at the point-of-use.