Specifications, Repairs – Banner RP-RM83F Rope Pull Switches User Manual
Page 7

•
Check for proper rope tension and adjust as needed
•
Verify free operation (no binding) of the rope and proper tripping when the rope is pulled
•
Periodically lubricate the pulleys and other moving parts associated with the rope
•
Repair any loose or damaged hardware, worn/frayed rope (cable), missing red rope sheathing or flags/markers (if
used)
•
Remove or clean off any contamination and eliminate its cause
Repairs
Contact Banner Engineering for troubleshooting of this device. Do not attempt any repairs to this Banner device; it
contains no field-replaceable components. If the device or a device component is determined to be defective by a
Banner Applications Engineer, they will advise you of Banner's RMA (Return Merchandise Authorization) procedure.
Important: If instructed to return the device, pack it with care. Damage that occurs in return shipping
is not covered by warranty.
Specifications
Contact Rating
10 A at 24 V ac
10 A at 110 V ac
6 A at 230 V ac
6 A at 24 V dc
2.5 kV max. transient tolerance
NEMA A300 P300
Monitoring Solid-State Output Rating
Rated operational voltage: Ue = 10 to 30 V dc
Rated operational current: = 50 mA
Utilization category: DC13
Protected against reverse polarity and short circuit
European Rating
Utilization categories: AC15 and DC13
Ui = 500 V ac; Ith = 10 A
Rated surge capacity: 2.5 kV
40-60 Hz
Ue (V)
Ie/AC-15 (A)
Ie/DC-13 (A)
120
6
0.55
240
3
0.27
Contact Material
Silver-nickel allow
Maximum Switching Speed
20 operations per minute
Recommended Rope Size
Accommodates rope sizes 2 to 5 mm diameter steel rope (see
Accessories); select rope diameter based on switch model and rope
length
75 m models: recommended 2 to 5 mm diameters
38 m models: recommended 2 to 5 mm diameters
Maximum Rope Pull Length
75 m (245 ft) or 37.5 m (123 ft), depending on model
Short Circuit Protection
10 amp Slow Blow, 15 amp Fast Blow. Recommended external
fusing or overload protection.
Mechanical Life
100,000 operations
Wire Connections
Screw terminals with pressure plates accept the following wire
sizes:
Stranded and solid: 20 AWG (0.5 mm2) to 16 AWG (1.5 mm2) for
one wire
Stranded: 20 AWG (0.5 mm2) to 18 AWG (1.0 mm2) for two wires
Cable Entry
M20 x 1.5 threaded entrance. Adapter supplied to convert M20 x
1.5 to ½"-14 NPT threaded entrance
Construction
Die-cast aluminum housing; zinc die-cast actuator
Environmental Rating
NEMA 4, IEC IP67, per IEC/EN 60529
Operating Conditions
Temperature: –30 °C to 80 °C (–34 °F to 176 °F)
Weight
RP-RM83F-..LT and -..LTE: 1Kg (2.1 lbs.)
RP-RM83F-..LR and -..LRE: 0.77 Kg (1.6 lbs.)
Product Performance Standards
DIN EN 60947-1, DIN EN 60947-5-1, DIN EN 60947-5-5, IEC
60947-1, IEC 60947-5-1, IEC 60947-5-5, ISO 13850
Certifications
RP-RM83F Heavy-Duty Rope Pull Emergency Stop Switches
P/N 141245 Rev. C
www.bannerengineering.com - tel: 763-544-3164