Specifications, Repairs – Banner RP-RM83F Rope Pull Switches User Manual

Page 7

background image

Check for proper rope tension and adjust as needed

Verify free operation (no binding) of the rope and proper tripping when the rope is pulled

Periodically lubricate the pulleys and other moving parts associated with the rope

Repair any loose or damaged hardware, worn/frayed rope (cable), missing red rope sheathing or flags/markers (if

used)

Remove or clean off any contamination and eliminate its cause

Repairs

Contact Banner Engineering for troubleshooting of this device. Do not attempt any repairs to this Banner device; it

contains no field-replaceable components. If the device or a device component is determined to be defective by a

Banner Applications Engineer, they will advise you of Banner's RMA (Return Merchandise Authorization) procedure.

Important: If instructed to return the device, pack it with care. Damage that occurs in return shipping

is not covered by warranty.

Specifications

Contact Rating

10 A at 24 V ac
10 A at 110 V ac
6 A at 230 V ac
6 A at 24 V dc
2.5 kV max. transient tolerance
NEMA A300 P300

Monitoring Solid-State Output Rating

Rated operational voltage: Ue = 10 to 30 V dc
Rated operational current: = 50 mA
Utilization category: DC13
Protected against reverse polarity and short circuit

European Rating

Utilization categories: AC15 and DC13
Ui = 500 V ac; Ith = 10 A
Rated surge capacity: 2.5 kV

40-60 Hz

Ue (V)

Ie/AC-15 (A)

Ie/DC-13 (A)

120

6

0.55

240

3

0.27

Contact Material

Silver-nickel allow

Maximum Switching Speed

20 operations per minute

Recommended Rope Size

Accommodates rope sizes 2 to 5 mm diameter steel rope (see

Accessories); select rope diameter based on switch model and rope

length
75 m models: recommended 2 to 5 mm diameters
38 m models: recommended 2 to 5 mm diameters

Maximum Rope Pull Length

75 m (245 ft) or 37.5 m (123 ft), depending on model

Short Circuit Protection

10 amp Slow Blow, 15 amp Fast Blow. Recommended external

fusing or overload protection.

Mechanical Life

100,000 operations

Wire Connections

Screw terminals with pressure plates accept the following wire

sizes:
Stranded and solid: 20 AWG (0.5 mm2) to 16 AWG (1.5 mm2) for

one wire
Stranded: 20 AWG (0.5 mm2) to 18 AWG (1.0 mm2) for two wires

Cable Entry

M20 x 1.5 threaded entrance. Adapter supplied to convert M20 x

1.5 to ½"-14 NPT threaded entrance

Construction

Die-cast aluminum housing; zinc die-cast actuator

Environmental Rating

NEMA 4, IEC IP67, per IEC/EN 60529

Operating Conditions

Temperature: –30 °C to 80 °C (–34 °F to 176 °F)

Weight

RP-RM83F-..LT and -..LTE: 1Kg (2.1 lbs.)
RP-RM83F-..LR and -..LRE: 0.77 Kg (1.6 lbs.)

Product Performance Standards

DIN EN 60947-1, DIN EN 60947-5-1, DIN EN 60947-5-5, IEC

60947-1, IEC 60947-5-1, IEC 60947-5-5, ISO 13850

Certifications

RP-RM83F Heavy-Duty Rope Pull Emergency Stop Switches

P/N 141245 Rev. C