beautypg.com

Appendix iii. fan performance (cont.) – Bryant 580J*04--12 User Manual

Page 63

background image

63

APPENDIX III. FAN PERFORMANCE (cont.)

580J*12

3 PHASE

10 TON HORIZONTAL SUPPLY

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Field---Supplied Drive

1

Standard Static Option

Medium Static Option

3000

579

0.70

660

0.89

732

1.09

799

1.29

860

1.50

3250

613

0.85

690

1.06

760

1.27

823

1.49

883

1.71

3500

648

1.03

721

1.25

788

1.48

850

1.71

907

1.95

3750

683

1.23

753

1.47

817

1.71

877

1.96

933

2.21

4000

719

1.45

786

1.71

848

1.97

905

2.23

959

2.50

4250

756

1.71

819

1.98

879

2.26

934

2.53

987

2.81

4500

792

1.99

853

2.28

910

2.57

964

2.87

1015

3.16

4750

830

2.31

888

2.62

943

2.92

995

3.23

1044

3.54

5000

867

2.66

923

2.98

976

3.30

1026

3.63

1074

3.95

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

High Static Option

3000

917

1.70

970

1.91

1021

2.13

1070

2.34

1117

2.56

3250

938

1.93

991

2.16

1041

2.38

1089

2.61

1134

2.85

3500

961

2.18

1013

2.42

1062

2.66

1108

2.91

1153

3.15

3750

985

2.46

1035

2.71

1083

2.97

1129

3.23

1173

3.49

4000

1011

2.76

1059

3.03

1106

3.30

1151

3.58

1194

3.85

4250

1037

3.09

1084

3.38

1130

3.66

1174

3.95

1216

4.24

4500

1064

3.46

1110

3.76

1155

4.06

1198

4.36

1239

4.66

4750

1091

3.85

1137

4.16

1180

4.48

1222

4.80

1263

5.12

5000

1120

4.28

1164

4.61

1207

4.94

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 53.

Boldface indicates field---supplied drive is required.

1. Recommend using field---supplied fan pulley (part no. KR11AD912) and belt (part no. KR29AF051).
2. Recommend using field---supplied motor pulley (part no. KR11HY410).

580J*12

3 PHASE

10 TON VERTICAL SUPPLY

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Standard Static Option

Medium Static Option

3000

616

0.79

689

0.97

757

1.16

821

1.36

882

1.57

3250

655

0.96

724

1.16

788

1.37

849

1.58

907

1.80

3500

695

1.17

760

1.38

821

1.60

879

1.83

934

2.06

3750

736

1.41

797

1.63

855

1.86

910

2.10

963

2.35

4000

777

1.68

834

1.91

889

2.16

942

2.41

993

2.67

4250

818

1.98

873

2.23

925

2.49

976

2.75

1025

3.02

4500

860

2.32

912

2.58

962

2.85

1010

3.13

1057

3.41

4750

902

2.69

951

2.97

999

3.26

1046

3.55

1091

3.84

5000

944

3.11

991

3.40

1037

3.70

1082

4.00

1125

4.31

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

High Static Option

3000

939

1.79

994

2.01

1047

2.24

1098

2.47

1147

2.71

3250

962

2.03

1015

2.26

1066

2.50

1115

2.75

1163

3.00

3500

987

2.30

1038

2.54

1088

2.80

1135

3.05

1181

3.32

3750

1014

2.60

1063

2.86

1111

3.12

1157

3.39

1202

3.66

4000

1042

2.93

1090

3.20

1136

3.48

1180

3.76

1224

4.04

4250

1072

3.30

1118

3.58

1162

3.87

1205

4.16

1247

4.46

4500

1103

3.70

1147

4.00

1190

4.29

1232

4.60

1273

4.91

4750

1135

4.14

1177

4.45

1219

4.76

1259

5.08

---

---

5000

1167

4.63

1209

4.95

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 53.

Boldface indicates field---supplied drive is required.

1. Recommend using field---supplied motor pulley (part no. KR11HY410).

580J