beautypg.com

Wiring diagrams, Pre--start--up, Warning – Bryant 580J*04--12 User Manual

Page 42

background image

42

when the potentiometer is approximately 9--v. The ac-

tuator should drive fully closed.

6. Turn the DCV and Exhaust potentiometers CCW until

the Exhaust LED turns on. The exhaust contacts will

close 30 to 120 seconds after the Exhaust LED turns

on.

7. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Connect a 9--v battery to AQ (positive node) and AQ1

(negative node). The DCV LED should turn on. The

actuator should drive to between 90 and 95% open.

3. Turn the DCV Maximum Position potentiometer to

midpoint. The actuator should drive to between 20

and 80% open.

4. Turn the DCV Maximum Position potentiometer to

fully CCW. The actuator should drive fully closed.

5. Turn the Minimum Position potentiometer to mid-

point. The actuator should drive to between 20 and

80% open.

6. Turn the Minimum Position Potentiometer fully CW.

The actuator should drive fully open.

7. Remove the jumper from TR and N. The actuator

should drive fully closed.

8. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

Supply--Air Sensor Input
To check supply--air sensor input:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Set the Enthalpy potentiometer to A. The Free Cool

LED turns on. The actuator should drive to between

20 and 80% open.

3. Remove the 5.6 kilo--ohm resistor and jumper T to

T1. The actuator should drive fully open.

4. Remove the jumper across T and T1. The actuator

should drive fully closed.

5. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

EconoMi$er IV Troubleshooting Completion
This procedure is used to return the EconoMi$er IV to

operation. No troubleshooting or testing is done by

performing the following procedure.

1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to previ-

ous setting.

4. Set minimum position, DCV setpoint, and exhaust po-

tentiometers to previous settings.

5. Remove 620--ohm resistor from terminals SR and +.
6. Remove 1.2 kilo--ohm checkout resistor from termin-

als SO and +. If used, reconnect sensor from termin-

als SO and +.

7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo--ohm resistor from T and T1. Recon-

nect wires at T and T1.

10. Remove jumper from P to P1. Reconnect device at P

and P1.

11. Apply power (24 vac) to terminals TR and TR1.

WIRING DIAGRAMS

See Fig. 52 and Fig. 53 for typical wiring diagrams.

PRE--START--UP

PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal

injury or death.

1. Follow recognized safety practices and wear pro-

tective goggles when checking or servicing refri-

gerant system.

2. Do not operate compressor or provide any electric

power to unit unless compressor terminal cover is

in place and secured.

3. Do not remove compressor terminal cover until

all electrical sources are disconnected.

4. Relieve all pressure from system before touching

or disturbing anything inside terminal box if refri-

gerant leak is suspected around compressor ter-

minals.

5. Never attempt to repair soldered connection while

refrigerant system is under pressure.

6. Do not use torch to remove any component. Sys-

tem contains oil and refrigerant under pressure.

To remove a component, wear protective goggles

and proceed as follows:

a. Shut off electrical power and then gas to unit.

b. Recover refrigerant to relieve all pressure from

system using both high--pressure and low

pressure ports.

c. Cut component connection tubing with tubing

cutter and remove component from unit.

d. Carefully unsweat remaining tubing stubs

when necessary. Oil can ignite when exposed

to torch flame.

!

WARNING

Proceed as follows to inspect and prepare the unit for

initial start--up:

1. Remove all access panels.
2. Read and follow instructions on all WARNING,

CAUTION, and INFORMATION labels attached to,

or shipped with, unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages such

as broken lines, loose parts, or disconnected

wires, etc.

580J