provided in the EconoMi$er IV wiring harness. (See Fig.

38.)

ECONOMI$ERIV

ECONOMI$ERIV
CONTROLLER

GROMMET

RETURN AIR
SENSOR

RETURN DUCT
(FIELD-PROVIDED)

C07085

Fig. 48 -- Return Air Temperature or Enthalpy Sensor

Mounting Location

In this mode of operation, the outdoor-air temperature is

compared to the return-air temperature and the lower

temperature airstream is used for cooling. When using this

mode of changeover control, turn the enthalpy setpoint

potentiometer fully clockwise to the D setting. (See Fig.

45.)
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part

number HH57AC078) is required. Replace the standard

outdoor dry bulb temperature sensor with the accessory

enthalpy sensor in the same mounting location. (See Fig.

39.) When the outdoor air enthalpy rises above the

outdoor enthalpy changeover setpoint, the outdoor-air

damper moves to its minimum position. The outdoor

enthalpy changeover setpoint is set with the outdoor

enthalpy setpoint potentiometer on the EconoMi$er IV

controller. The setpoints are A, B, C, and D. (See Fig. 46.)

The factory-installed 620-ohm jumper must be in place

across terminals S

R

and SR+ on the EconoMi$er IV

controller.
Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV

controller uses two enthalpy sensors (HH57AC078 and

CRENTDIF004A00), one in the outside air and one in the

return air duct. The EconoMi$er IV controller compares

the outdoor air enthalpy to the return air enthalpy to

determine EconoMi$er IV use. The controller selects the

lower enthalpy air (return or outdoor) for cooling. For

example, when the outdoor air has a lower enthalpy than

the return air, the EconoMi$er IV opens to bring in

outdoor air for free cooling.
Replace the standard outside air dry bulb temperature

sensor with the accessory enthalpy sensor in the same

mounting location. (See Fig. 39.) Mount the return air

enthalpy sensor in the return air duct. (See Fig. 48.)

Wiring is provided in the EconoMi$er IV wiring harness.

(See Fig. 41.) The outdoor enthalpy changeover setpoint is

set with the outdoor enthalpy setpoint potentiometer on

the EconoMi$er IV controller. When using this mode of

changeover

control,

turn

the

enthalpy

setpoint

potentiometer fully clockwise to the D setting.

CONTROL

CURVE

A
B
C
D

CONTROL POINT

APPROX.

deg. F (deg. C)

AT 50% RH

73 (23)
70 (21)
67 (19)
63 (17)

12

1

4

16

18

20

22

24

26

28

30

32

3

4

36

38

40

42

44

46

9

0

1

0

0

80

70

6

0

50

40

30

20

10

ENTHALPY BTU PER POUND DRY AIR

85

(29)

90

(32)

95

(35)

100

(38)

105

(41)

110

(43)

35

(2)

35

(2)

40

(4)

40

(4)

105

(41)

110

(43)

45

(7)

45

(7)

50

(10)

50

(10)

55

(13)

55

(13)

60

(16)

60

(16)

65

(18)

65

(18)

70

(21)

70

(21)

75

(24)

75

(24)

80

(27)

80

(27)

85

(29)

90

(32)

95

(35)

100

(38)

A

A

B

B

C

C

D

D

RELATIVE HUMIDITY (%)

HIGH LIMIT

CURVE

APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)

C06037

Fig. 49 -- Enthalpy Changeover Setpoints

580J