S

Wire terminal tightness

S

Refrigerant charge level

S

Evaporator coil cleaning

S

Evaporator blower motor amperage

Heating

S

Heat exchanger flue passageways cleanliness

S

Gas burner condition

S

Gas manifold pressure

S

Heating temperature rise

Economizer or Outside Air Damper

S

Inlet filters condition

S

Check damper travel (economizer)

S

Check gear and dampers for debris and dirt

Air Filters and Screens
Each unit is equipped with return air filters. If the unit has

an economizer, it will also have an outside air screen. If a

manual outside air damper is added, an inlet air screen

will also be present.

Each of these filters and screens will need to be

periodically replaced or cleaned.
Return Air Filters
Return air filters are disposable fiberglass media type.

Access to the filters is through the small lift--out panel

located on the rear side of the unit, above the

evaporator/return air access panel. (See Fig. 1.)

To remove the filters:

1. Grasp the bottom flange of the upper panel.
2. Lift up and swing the bottom out until the panel dis-

engages and pulls out.

3. Reach inside and extract the filters from the filter

rack.

4. Replace these filters as required with similar replace-

ment filters of same size.

To re--install the access panel:

1. Slide the top of the panel up under the unit top panel.
2. Slide the bottom into the side channels.
3. Push the bottom flange down until it contacts the top

of the lower panel (or economizer top).

IMPORTANT: DO NOT OPERATE THE UNIT
WITHOUT THESE FILTERS!
Outside Air Hood
Outside

air

hood

inlet

screens

are

permanent

aluminum--mesh type filters. Check these for cleanliness.

Remove the screens when cleaning is required. Clean by

washing with hot low--pressure water and soft detergent

and replace all screens before restarting the unit. Observe

the flow direction arrows on the side of each filter frame.
Economizer Inlet Air Screen
This air screen is retained by spring clips under the top

edge of the hood. (See Fig. 3.)

17 1/4”

DIVIDER

BAROMETRIC

RELIEF

CLEANABLE

ALUMINUM

FILTER

FILTER

HOOD

FILTER

CLIP

OUTSIDE

AIR

C06027

Fig. 3 -- Filter Installation

To remove the filter, open the spring clips. Re--install the

filter by placing the frame in its track, then closing the

spring clips.
Manual Outside Air Hood Screen
This inlet screen is secured by a retainer angle across the

top edge of the hood. (See Fig. 4.)

C07156

Fig. 4 -- Screens Installed on Outdoor--Air Hood

(Sizes 7--1/2 to 12--1/2 Tons Shown)

To remove the screen, loosen the screws in the top retainer

and slip the retainer up until the filter can be removed.

580J