beautypg.com

Appendix ii. physical data (cont.), Physical data (heating) 7.5 tons – Bryant 580J*04--12 User Manual

Page 52

background image

52

APPENDIX II. PHYSICAL DATA (cont.)

Physical Data (Heating)

7.5 -- 10 TONS

580J*04

580J*05

580J*06

580J*07

Gas Connection

# of Gas Valves

1

1

1

1

Nat. gas supply line press (in. w.g.)/(PSIG)

4---13 / 0.18---0.47

4---13 / 0.18---0.47

4---13 / 0.18---0.47

4---13 / 0.18---0.47

LP supply line press (in. w.g.)/(PSIG)

11---13 / 0.40---0.47

11---13 / 0.40---0.47

11---13 / 0.40---0.47

11---13 / 0.40---0.47

Heat Anticipator Setting (Amps)

1st stage

0.14

0.14

0.14

0.14

2nd stage

0.14

0.14

0.14

0.14

Natural Gas Heat

Connection size

1/2” NPT

1/2” NPT

1/2” NPT

1/2” NPT

LO

W

# of stages / # of burners (total)

1 / 2

1 / 2

1 / 2

1 / 2

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

195 / 115

Temperature rise (min/max)

25 / 55

25 --- 55

25 --- 55

25 --- 55

Connection size

1/2” NPT

1/2” NPT

1/2” NPT

1/2” NPT

MED

# of stages / # of burners (total)

1 or 2 / 3

1 / 3

1 / 3

1 / 3

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

195 / 115

Temperature rise (min/max)

55 / 85

35 / 65

35 / 65

35 / 65

Connection size

1/2” NPT

1/2” NPT

1/2” NPT

1/2” NPT

HI

G

H

# of stages / # of burners (total)

---

1 or 2 / 3

1 or 2 / 3

1 or 2 / 3

Rollout switch opens / Closes

---

195 / 115

195 / 115

195 / 115

Temperature rise (min/max)

---

50 / 80

50 / 80

50 / 80

Liquid Propane Heat

Connection size

1/2” NPT

1/2” NPT

1/2” NPT

1/2” NPT

LO

W

# of stages / # of burners (total)

1 / 2

1 / 2

1 / 2

1 / 2

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

195 / 115

Temperature rise (min/max)

25 / 55

25 --- 55

25 --- 55

25 --- 55

Connection size

1/2” NPT

1/2” NPT

1/2” NPT

1/2” NPT

MED

# of stages / # of burners (total)

1 or 2 / 3

1 or 2 / 3

1 or 2 / 3

1 or 2 / 3

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

195 / 115

Temperature rise (min/max)

55 / 85

35 / 65

35 / 65

35 / 65

Connection size

1/2” NPT

1/2” NPT

1/2” NPT

1/2” NPT

HI

G

H

# of stages / # of burners (total)

---

1 or 2 / 3

1 or 2 / 3

1 or 2 / 3

Rollout switch opens / Closes

---

195 / 115

195 / 115

195 / 115

Temperature rise (min/max)

---

50 / 80

50 / 80

50 / 80

Low NO

x

Gas Heat

Connection size

1/2” NPT

1/2” NPT

1/2” NPT

1/2” NPT

LO

W

# of stages / # of burners (total)

1 / 2

1 / 2

1 / 2

---

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

---

Temperature rise (min/max)

20 / 50

20 / 50

20 / 50

---

Connection size

1/2” NPT

1/2” NPT

1/2” NPT

1/2” NPT

MED

# of stages / # of burners (total)

1 / 3

1 / 3

1 / 3

---

Rollout switch opens / closes

195 / 115

195 / 115

195 / 115

---

Temperature rise (min/max)

30 / 60

30 / 60

30 / 60

---

Connection size

1/2” NPT

1/2” NPT

1/2” NPT

1/2” NPT

HI

G

H

# of stages / # of burners (total)

---

1 / 3

1 / 3

---

Rollout switch opens / Closes

---

195 / 115

195 / 115

---

Temperature rise (min/max)

---

40 / 70

40 / 70

---

580J