beautypg.com

Bryant 580J*04--12 User Manual

Page 40

background image

40

5. Carefully

adjust

the

minimum

position

potentiometer until the measured mixed air

temperature matches the calculated value.

6. Reconnect the supply air sensor to terminals T and

T1.

Remote control of the EconoMi$er IV damper is desirable

when requiring additional temporary ventilation. If a

field-supplied remote potentiometer (Honeywell part

number S963B1128) is wired to the EconoMi$er IV

controller, the minimum position of the damper can be

controlled from a remote location.
To control the minimum damper position remotely,

remove the factory-installed jumper on the P and P1

terminals on the EconoMi$er IV controller. Wire the

field-supplied potentiometer to the P and P1 terminals on

the EconoMi$er IV controller. (See Fig. 41.)
Damper Movement
Damper movement from full open to full closed (or vice

versa) takes 2--1/2 minutes.
Thermostats
The EconoMi$er IV control works with conventional

thermostats that have a Y1 (cool stage 1), Y2 (cool stage

2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The

EconoMi$er IV control does not support space

temperature sensors. Connections are made at the

thermostat terminal connection board located in the main

control box.
Occupancy Control
The factory default configuration for the EconoMi$er IV

control is occupied mode. Occupied status is provided by

the black jumper from terminal TR to terminal N. When

unoccupied mode is desired, install a field--supplied

timeclock function in place of the jumper between TR and

N. (See Fig. 41.) When the timeclock contacts are closed,

the EconoMi$er IV control will be in occupied mode.

When the timeclock contacts are open (removing the 24--v

signal from terminal N), the EconoMi$er IV will be in

unoccupied mode.
Demand Control Ventilation (DCV)
When using the EconoMi$er IV for demand controlled

ventilation, there are some equipment selection criteria

which should be considered. When selecting the heat

capacity and cool capacity of the equipment, the

maximum ventilation rate must be evaluated for design

conditions. The maximum damper position must be

calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to

10% more than the typical cfm required per person, using

normal outside air design criteria.
A proportional anticipatory strategy should be taken with

the following conditions: a zone with a large area, varied

occupancy, and equipment that cannot exceed the required

ventilation rate at design conditions. Exceeding the

required ventilation rate means the equipment can

condition air at a maximum ventilation rate that is greater

than the required ventilation rate for maximum

occupancy. A proportional-anticipatory strategy will cause

the fresh air supplied to increase as the room CO

2

level

increases even though the CO

2

setpoint has not been

reached. By the time the CO

2

level reaches the setpoint,

the damper will be at maximum ventilation and should

maintain the setpoint.
In order to have the CO

2

sensor control the economizer

damper in this manner, first determine the damper voltage

output for minimum or base ventilation. Base ventilation

is the ventilation required to remove contaminants during

unoccupied periods. The following equation may be used

to determine the percent of outside air entering the

building for a given damper position. For best results there

should be at least a 10 degree difference in outside and

return-air temperatures.

(T

O x

OA

) + (TR

x

RA

) =T

M

100

100

T

O

= Outdoor-Air Temperature

OA = Percent of Outdoor Air
T

R

= Return-Air Temperature

RA = Percent of Return Air
T

M

= Mixed-Air Temperature

Once base ventilation has been determined, set the

minimum damper position potentiometer to the correct

position.
The same equation can be used to determine the occupied

or maximum ventilation rate to the building. For example,

an output of 3.6 volts to the actuator provides a base

ventilation rate of 5% and an output of 6.7 volts provides

the maximum ventilation rate of 20% (or base plus 15 cfm

per person). Use Fig. 51 to determine the maximum

setting of the CO

2

sensor. For example, an 1100 ppm

setpoint relates to a 15 cfm per person design. Use the

1100 ppm curve on Fig. 51 to find the point when the CO

2

sensor output will be 6.7 volts. Line up the point on the

graph with the left side of the chart to determine that the

range configuration for the CO

2

sensor should be 1800

ppm. The EconoMi$er IV controller will output the 6.7

volts from the CO

2

sensor to the actuator when the CO

2

concentration in the space is at 1100 ppm. The DCV

setpoint may be left at 2 volts since the CO

2

sensor

voltage will be ignored by the EconoMi$er IV controller

until it rises above the 3.6 volt setting of the minimum

position potentiometer.
Once the fully occupied damper position has been

determined, set the maximum damper demand control

ventilation potentiometer to this position. Do not set to the

maximum position as this can result in over-ventilation to

the space and potential high humidity levels.
CO

2

Sensor Configuration

The CO

2

sensor has preset standard voltage settings that

can be selected anytime after the sensor is powered up.

(See Table 17.)
Use setting 1 or 2 for Bryant equipment. (See Table 17.)

1. Press Clear and Mode buttons. Hold at least 5

seconds until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.

580J