Economi$er iv – Bryant 580J*04--12 User Manual

Page 36

background image

36

C06053

Fig. 43 -- EconoMi$er IV Functional View

EconoMi$er IV

Table 15 provides a summary of EconoMi$er IV.

Troubleshooting instructions are enclosed.

A functional view of the EconoMi$er is shown in Fig. 43.

Typical settings, sensor ranges, and jumper positions are

also shown. An EconoMi$er IV simulator program is

available from Bryant to help with EconoMi$er IV

training and troubleshooting.
EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10

to 20 mA device used to measure the outdoor-air

temperature. The outdoor-air temperature is used to

determine when the EconoMi$er IV can be used for free

cooling. The sensor is factory-installed on the

EconoMi$er IV in the outdoor airstream. (See Fig. 44.)

The operating range of temperature measurement is 40_ to

100_F (4_ to 38_C).
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor

located at the inlet of the indoor fan. (See Fig. 44.) This

sensor is factory installed. The operating range of

temperature measurement is 0° to 158_F (--18_ to 70_C).

See Table 16 for sensor temperature/resistance values.

Table 16 – Thermistor Resistance vs Temperature

Values for Space Temperature Sensor, Supply Air

Temperature Sensor, and Outdoor Air Temperature

Sensor

TEMP

(C)

TEMP

(F)

RESISTANCE

(Ohms)

---40

---40

335,651

---35

---31

242,195

---30

---22

176,683

---25

---13

130,243

---20

---4

96,974

---15

5

72,895

---10

14

55,298

---5

23

42,315

0

32

32,651

5

41

25,395

10

50

19,903

15

59

15,714

20

68

12,494

25

77

10,000

30

86

8,056

35

95

6,530

40

104

5,325

45

113

4,367

50

122

3,601

55

131

2,985

60

140

2,487

65

149

2,082

70

158

1,752

580J