setting below the room temperature and verify that the

burners and evaporator fan turn off.

Refer to Table 11 and Table 12 for the correct orifice to

use at high altitudes.

Heating

1. Purge gas supply line of air by opening union ahead

of the gas valve. If gas odor is detected, tighten union

and wait 5 minutes before proceeding.

2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan

switch at AUTO. or ON position. Set heating temper-

ature lever above room temperature.

4. The induced--draft motor will start.
5. After a call for heating, the main burners should light

within 5 seconds. If the burner does not light, then

there is a 22--second delay before another 5--second

try. If the burner still does not light, the time delay is

repeated. If the burner does not light within 15

minutes, there is a lockout. To reset the control, break

the 24 v power to W1.

6. The evaporator--fan motor will turn on 45 seconds

after burner ignition.

7. The evaporator--fan motor will turn off in 45 seconds

after the thermostat temperature is satisfied.

8. Adjust airflow to obtain a temperature rise within the

range specified on the unit nameplate.

NOTE: The default value for the evaporator--fan motor
on/off delay is 45 seconds. The Integrated Gas Unit
Controller (IGC) modifies this value when abnormal limit
switch cycles occur. Based upon unit operating conditions,

the on delay can be reduced to 0 seconds and the off delay
can be extended to 180 seconds. When one flash of the
LED is observed, the evaporator--fan on/off delay has
been modified.
If the limit switch trips at the start of the heating cycle

during the evaporator on delay, the time period of the on

delay for the next cycle will be 5 seconds less than the

time at which the switch tripped. (Example: If the limit

switch trips at 30 seconds, the evaporator--fan on delay for

the next cycle will occur at 25 seconds.) To prevent

short--cycling, a 5--second reduction will only occur if a

minimum of 10 minutes has elapsed since the last call for

heating.

The evaporator--fan off delay can also be modified. Once

the call for heating has ended, there is a 10--minute period

during which the modification can occur. If the limit

switch trips during this period, the evaporator--fan off

delay will increase by 15 seconds. A maximum of 9 trips

can occur, extending the evaporator--fan off delay to 180

seconds.

To restore the original default value, reset the power to the

unit.

To shut off unit, set system selector switch at OFF

position. Resetting heating selector lever below room

temperature will temporarily shut unit off until space

temperature falls below thermostat setting.

Ventilation (Continuous Fan)

Set fan and system selector switches at ON and OFF

positions,

respectively.

Evaporator

fan

operates

continuously to provide constant air circulation. When the

evaporator--fan selector switch is turned to the OFF

position, there is a 30--second delay before the fan turns

off.

OPERATING SEQUENCES

Cooling, Unit Without Economizer

When thermostat calls for cooling, terminals G and Y1 are

energized.

The

indoor--fan

contactor

(IFC)

and

compressor contactor are energized and indoor--fan motor,

compressor, and outdoor fan start. The outdoor fanmotor

runs continuously while unit is cooling.

Heating, Unit Without Economizer

When the thermostat calls for heating, terminal W1 is

energized. To prevent thermostat short--cycling, the unit is

locked into the Heating mode for at least 1 minute when

W1 is energized. The induced--draft motor is energized

and the burner ignition sequence begins. The indoor

(evaporator) fan motor (IFM) is energized 45 seconds

after a flame is ignited. On units equipped for two stages

of heat, when additional heat is needed, W2 is energized

and the high--fire solenoid on the main gas valve (MGV)

is energized. When the thermostat is satisfied and W1 is

deenergized, the IFM stops after a 45--second time--off

delay.

Cooling, Unit With EconoMi$er IV

For Occupied mode operation of EconoMi$er IV, there

must be a 24--v signal at terminals TR and N (provided

through PL6--3 from the unit’s IFC coil). Removing the

signal at N places the EconoMi$er IV control in

Unoccupied mode.

During Occupied mode operation, indoor fan operation

will be accompanied by economizer dampers moving to

Minimum Position setpoint for ventilation. If indoor fan is

off, dampers will close. During Unoccupied mode

operation, dampers will remain closed unless a Cooling

(by free cooling) or DCV demand is received.

Integrated EconoMi$er IV operation on 580J single

compressor model requires a 2--stage thermostat (Y1 and

Y2 switches).

When free cooling using outside air is not available, the

unit cooling sequence will be controlled directly by the

space thermostat as described above as Cooling, Without

Economizer. Outside air damper position will be closed or

Minimum Position as determined by occupancy mode and

fan signal.

When free cooling is available as determined by the

appropriate changeover command (dry bulb, outdoor

enthalpy, differential dry bulb or differential enthalpy), a

call for cooling (Y1 closes at the thermostat) will cause

the economizer control to modulate the dampers open and

closed to maintain the unit supply air temperature at 50 to

55_F. Compressor will not run.

580J