beautypg.com

Unit arrangement and access, Warning – Bryant 580J*04--12 User Manual

Page 2

background image

2

ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal

injury or death.
Before performing service or maintenance operations

on unit, turn off main power switch to unit. Electrical

shock and rotating equipment could cause injury.

!

WARNING

ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal

injury or death.
Units with convenience outlet circuits may use

multiple disconnects. Check convenience outlet for

power status before opening unit for service. Locate

its disconnect switch, if appropriate, and open it.

Tag--out this switch, if necessary.

!

WARNING

UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal

injury, death and/or equipment damage.
Puron (R410A) refrigerant systems operate at higher

pressures than standard R--22 systems. Do not use

R--22 service equipment or components on Puron

refrigerant equipment.

!

WARNING

FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal

injury or death.
Disconnect gas piping from unit when pressure testing

at pressure greater than 0.5 psig. Pressures greater

than 0.5 psig will cause gas valve damage resulting in

hazardous condition. If gas valve is subjected to

pressure greater than 0.5 psig, it must be replaced

before use. When pressure testing field-supplied gas

piping at pressures of 0.5 psig or less, a unit connected

to such piping must be isolated by closing the manual

gas valve(s).

!

WARNING

UNIT ARRANGEMENT AND ACCESS

General

Fig. 1 and Fig. 2 show general unit arrangement and

access locations.

FILTER ACCESS PANEL

OUTDOOR-AIR OPENING AND

INDOOR COIL ACCESS PANEL

COMPRESSOR

ACCESS PANEL (04-07 only)

C08449

Fig. 1 -- Typical Access Panel Locations

BLOWER
ACCESS
PANEL

CONTROL BOX

COMPRESSOR
(08-12 only)

C08450

Fig. 2 -- Blower Access Panel Location

Routine Maintenance

These items should be part of a routine maintenance

program, to be checked every month or two, until a

specific schedule for each can be identified for this

installation:
Quarterly Inspection (and 30 days after initial start)

S

Return air filter replacement

S

Outdoor hood inlet filters cleaned

S

Belt tension checked

S

Belt condition checked

S

Pulley alignment checked

S

Fan shaft bearing locking collar tightness checked

S

Condenser coil cleanliness checked

S

Condensate drain checked

Seasonal Maintenance

These items should be checked at the beginning of each

season (or more often if local conditions and usage

patterns dictate):
Air Conditioning

S

Condenser fan motor mounting bolts tightness

S

Compressor mounting bolts

S

Condenser fan blade positioning

S

Control box cleanliness and wiring condition

580J