Orifice replacement – Bryant 580J*04--12 User Manual
Page 28
28
Table 8 – LED Error Code Description*
LED INDICATION
ERROR CODE
DESCRIPTION
ON
Normal Operation
OFF
Hardware Failure
1 Flash{
Evaporator Fan On/Off Delay Modified
2 Flashes
Limit Switch Fault
3 Flashes
Flame Sense Fault
4 Flashes
4 Consecutive Limit Switch Faults
5 Flashes
Ignition Lockout Fault
6 Flashes
Induced---Draft Motor Fault
7 Flashes
Rollout Switch Fault
8 Flashes
Internal Control Fault
9 Flashes
Software Lockout
LEGEND
LED --- Light Emitting Diode
* A 3---second pause exists between LED error code flashes. If
more than one error code exists, all applicable codes will be
displayed in numerical sequence.
{
Indicates a code that is not an error. The unit will continue to
operate when this code is displayed.
IMPORTANT: Refer to Troubleshooting Table 13 and
Table 14 for additional information.
Orifice Replacement
This unit uses orifice type LH32RFnnn (where nnn
indicates orifice reference size). When replacing unit
orifices, order the necessary parts via RCD. See Table 10
for available orifice sizes. See Table 11 and Table 12 for
orifice sizes for Natural Gas and LP fuel usage at various
elevations above sea level.
Check that each replacement orifice is tight at its threads
into the manifold pipe and that orifice projection does not
exceed maximum value. See Fig. 32.
Single Stage
2 Stage
C08210
Fig. 37 -- Gas Valves