Control Circuit, 24--V

The control circuit is protected against overcurrent

conditions by a circuit breaker mounted on control

transformer TRAN. Reset is manual.

GAS HEATING SYSTEM

580J unit heating systems are referenced here according to

unit Gas Heat Option (defined in the unit model number

Position#8) and Heat Level (input capacity, defined in

Positions #9--10--11). See Appendix 1 for a complete unit

model number nomenclature chart.

POSITION #8

GAS HEAT OPTION

A

Nat. Gas / Standard HX and Heat

B

Nat. Gas / SS HX and Low NO

x

Heat

C

Nat. Gas / SS HX and Standard Heat

General

The heat exchanger system consists of a gas valve feeding

multiple inshot burners off a manifold. The burners fire

into matching primary tubes. The primary tubes discharge

into combustion plenum where gas flow converges into

secondary tubes. The secondary tubes exit into the

induced draft fan wheel inlet. The induced fan wheel

discharges into a flue passage and flue gases exit out a

flue hood on the side of the unit. The induced draft fan

motor includes a Hall Effect sensor circuit that confirms

adequate wheel speed via the Integrated Gas Control

(IGC) board. Safety switches include a Rollout Switch (at

the top of the burner compartment) and a limit switch

(mounted through the fan deck, over the tubes). (See Fig.

27 and Fig. 28.)

INDUCED-

DRAFT

MOTOR

MOUNTING

PLATE

INDUCED-

DRAFT

MOTOR

MANIFOLD

PRESSURE

TAP

VESTIBULE

PLATE

FLUE

EXHAUST

ROLLOUT

SWITCH

BLOWER

HOUSING

GAS

VALVE

BURNER

SECTION

C06152

Fig. 27 -- Burner Section Details

Limit Switch
and Shield

C08284

Fig. 28 -- Limit Switch Location

Fuel Types and Pressures

Natural Gas — The 580J unit is factory--equipped for use

with Natural Gas fuel at elevation under 2000 ft (610 m).

See section Orifice Replacement for information in

modifying this unit for installation at elevations above

2000 ft (610 m).

Gas line pressure entering the unit’s main gas valve must

be within specified ranges. Adjust unit gas regulator valve

as required or consult local gas utility.

Table 4 – Natural Gas Supply Line Pressure Ranges

580J SIZE

GAS

HEAT OPT

HEAT

LEVEL

MIN

MAX

All

All

All

4.0 in. wg

(996 Pa)

13.0 in. wg

(3240 Pa)

Manifold pressure is factory--adjusted for NG fuel use.

Adjust as required to obtain best flame characteristic.

Table 5 – Natural Gas Manifold Pressure Ranges

GAS

HEAT

OPT

HEAT

LEVEL

HIGH

FIRE

LOW

FIRE

RANGE

A, C

All

3.5 in. wg

(872 Pa)

1.7 in. wg

(423 Pa){

2.0---5.0 in. wg (Hi)

(498---1245 Pa)

B

All

3.5 in. wg

(872 Pa)

NA

2.0---5.0 in. wg (Hi)

(498---1245 Pa)

NA: Not Available
{

3 Phase models only

Liquid Propane — Accessory packages are available for

field--installation that will convert the 580J unit (except

low NO

x

model) to operate with Liquid Propane (LP)

fuels. These kits include new orifice spuds, new springs

for gas valves and a supply line low pressure switch. See

section on Orifice Replacement for details on orifice size

selections.

Low NO

x

models include specially--sized orifices and use

of different flue flow limits and tube baffles. Because of

these extra features, conversion of these models to LP is

not recommended.

Fuel line pressure entering unit gas valve must remain

within specified range.

580J