beautypg.com

Appendix ii. physical data (cont.), Physical data (heating) 3 tons – Bryant 580J*04--12 User Manual

Page 51

background image

51

APPENDIX II. PHYSICAL DATA (cont.)

Physical Data (Heating)

3 -- 6 TONS

580J*04

580J*05

580J*06

580J*07

Gas Connection

# of Gas Valves

1

1

1

1

Connection size

1/2” NPT

1/2” NPT

1/2” NPT

1/2” NPT

Nat. gas supply line press (in. w.g.)/(PSIG)

5---13 / 0.18---0.47

5---13 / 0.18---0.47

5---13 / 0.18---0.47

5---13 / 0.18---0.47

LP supply line press (in. w.g.)/(PSIG)

11---13 / 0.40---0.47

11---13 / 0.40---0.47

11---13 / 0.40---0.47

11---13 / 0.40---0.47

Heat Anticipator Setting (Amps)

1st stage

0.14

0.14

0.14

0.14

2nd stage

0.14

0.14

0.14

0.14

Natural Gas Heat

LO

W

# of stages / # of burners (total)

1 / 2

1 / 2

1 / 2

1 / 2

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

195 / 115

Temperature rise

25 / 55

25 --- 55

25 --- 55

25 --- 55

MED

# of stages / # of burners (total)

1 or 2 / 3

1 / 3

1 / 3

1 / 3

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

195 / 115

Temperature rise

55 / 85

35 / 65

35 / 65

35 / 65

HI

G

H

# of stages / # of burners (total)

---

1 or 2 / 3

1 or 2 / 3

1 or 2 / 3

Rollout switch opens / Closes

---

195 / 115

195 / 115

195 / 115

Temperature rise

---

50 / 80

50 / 80

50 / 80

Liquid Propane Heat

LO

W

# of stages / # of burners (total)

1 / 2

1 / 2

1 / 2

1 / 2

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

195 / 115

Temperature rise

25 / 55

25 --- 55

25 --- 55

25 --- 55

MED

# of stages / # of burners (total)

1 or 2 / 3

1 or 2 / 3

1 or 2 / 3

1 or 2 / 3

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

195 / 115

Temperature rise

55 / 85

35 / 65

35 / 65

35 / 65

HI

G

H

# of stages / # of burners (total)

---

1 or 2 / 3

1 or 2 / 3

1 or 2 / 3

Rollout switch opens / Closes

---

195 / 115

195 / 115

195 / 115

Temperature rise

---

50 / 80

50 / 80

50 / 80

Low NO

x

Gas Heat

LO

W

# of stages / # of burners (total)

1 / 2

1 / 2

1 / 2

---

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

---

Temperature rise

20 / 50

20 / 50

20 / 50

---

MED

# of stages / # of burners (total)

1 / 3

1 / 3

1 / 3

---

Rollout switch opens / closes

195 / 115

195 / 115

195 / 115

---

Temperature rise

30 / 60

30 / 60

30 / 60

---

HI

G

H

# of stages / # of burners (total)

---

1 / 3

1 / 3

---

Rollout switch opens / Closes

---

195 / 115

195 / 115

---

Temperature rise

---

40 / 70

40 / 70

---

580J