During free cooling operation, a supply air temperature

(SAT) above 50_F will cause the dampers to modulate

between Minimum Position setpoint and 100% open. With

SAT from 50_F to 45_F, the dampers will maintain at the

Minimum Position setting. With SAT below 45_F, the

outside air dampers will be closed. When SAT rises to

48_F, the dampers will re--open to Minimum Position

setting.

Should 100% outside air not be capable of satisfying the

space temperature, space temperature will rise until Y2 is

closed. The economizer control will call for compressor

operation. Dampers will modulate to maintain SAT at 50

to 55_F concurrent with compressor operation. The Low

Ambient Lockout Thermostat will block compressor

operation with economizer operation below 42_F outside

air temperature.

When space temperature demand is satisfied (thermostat

Y1 opens), the dampers will return to Minimum Damper

position if indoor fan is running or fully closed if fan is

off.

If accessory power exhaust is installed, the power exhaust

fan motors will be energized by the economizer control as

the dampers open above the PE--On setpoint and will be

de--energized as the dampers close below the PE--On

setpoint.

Damper movement from full closed to full open (or vice

versa) will take between 1--1/2 and 2--1/2 minutes.

Heating With EconoMi$er IV

During Occupied mode operation, indoor fan operation

will be accompanied by economizer dampers moving to

Minimum Position setpoint for ventilation. If indoor fan is

off, dampers will close. During Unoccupied mode

operation, dampers will remain closed unless a DCV

demand is received.

When the room temperature calls for heat (W1 closes), the

heating controls are energized as described in Heating,

Unit Without Economizer above.

Demand Controlled Ventilation

If a field--installed CO

2

sensor is connected to the

EconoMi$er IV control, a Demand Controlled Ventilation

strategy will operate automatically. As the CO

2

level in

the space increases above the CO

2

setpoint (on the

EconoMi$er IV controller), the minimum position of the

dampers will be increased proportionally, until the

Maximum Ventilation setting is reached. As the space

CO

2

level decreases because of the increase in fresh air,

the outdoor--damper will follow the higher demand

condition from the DCV mode or from the free--cooling

mode.

DCV operation is available in Occupied and Unoccupied

periods with EconoMi$er IV. However, a control

modification will be required on the 580J unit to

implement the Unoccupied period function.

FASTENER TORQUE VALUES

See Table 18 for torque values.

Table 18 – Torque Values

Supply fan motor mounting

120 +/--- 12 in---lbs

Supply fan motor adjustment plate

120 +/--- 12 in---lbs

Motor pulley setscrew

72+/--- 5 in---lbs

Fan pulley setscrew

72+/--- 5 in---lbs

Blower wheel hub setscrew

72+/--- 5 in---lbs

Bearing locking collar setscrew

65---70 in---lbs

Compressor mounting bolts

65---75 in---lbs

Condenser fan motor mounting bolts

20 +/--- 2 in---lbs

Condenser fan hub setscrew

84 +/--- 12 in---lbs