Rockwell Automation SA3100 Distributed Power System Drv Config,Program User Manual
Page 87
Configuring the UDC Module’s Registers
3-49
Run Time AC Power Technology Hardware Faults (Continued):
DC Bus Pre-charge Faults:
Diagnostic Fault Code Register (Continued)
222/1222
Code
Fault
Description/Action
22
A/D interrupt overrun
An interrupt from the power technology
circuit was detected before the previous
interrupt was processed. Replace the
PMI Regulator motherboard.
23
Gate power test 1 fault
Gate power is on when the MCR is off
and Gate Enable is on. Replace the PMI
Regulator motherboard.
24
Not used.
25
Gate power test 3 fault
Gate power is on when the MCR is off
and Gate Enable is on. Replace the PMI
Regulator motherboard.
26
Gate power loss
Loss of gate power feedback while in
run. Replace the PMI Regulator
motherboard.
Code
Fault
Description/Action
100
Pre-charge closed
Pre-charge is requested to close when
Pre-charge is already closed.
101
Pre-charge did not close
The pre-charge did not close within 2
seconds.
102
Pre-charge open
Pre-charge is closed but AC power
technology status indicates it is open.
103
Pre-charge did not open
Pre-charge is commanded to open but
does not do so after one second.
104
Pre-charge opened
The AC power technology circuit
detected that the pre-charge opened
while in run.
105
No used
106
Charge time-out
Minimum bus voltage is not detected
within 10 seconds after bus enable.
107
AC line fault
AC line status from Power Module not
detected.
108
Charge ripple fault
DC ripple voltage above tolerance.
200
Diag_12V PS
Isolated 12V power supply is out of
tolerance.
201
Diag_PS_Ext_PS
External ±15V power supply (for G or
H-frame units) is out of tolerance.