Configuring the UDC Module’s Registers
3-43
Interlock Register (Continued)
205/1205
RPI Missing
Bit 2
The RPI Missing bit is set if the Run
Permissive input on the Resolver & Drive
I/O board is not on.
Hex Value:
0004H
Sug. Var. Name:
IC_RPI@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Faults Need Reset
Bit 3
The Faults Need Reset bit is set if previous
faults (register 202/1202) have not been
cleared.
Hex Value:
0008H
Sug. Var. Name:
IC_FLT@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Rising Edge Required
Bit 4
The Rising Edge Required bit is set if a
rising edge is not detected on a command
bit in register 100/1100.
Hex Value:
0010H
Sug. Var. Name:
IC_RISE@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
This interlock bit will be set if the application task has set the Fault Reset bit (register
100/1100, bit 8) but has not cleared and then re-enabled any command bits.
More Than One Request
Bit 5
The More Than One Request bit is set if
more than one operating mode is requested
at a time in register 100/1100 (bits 0, 1, 2).
Hex Value:
0020H
Sug. Var. Name:
IC_MORE@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Bus Not Ready
Bit 6
The Bus Not Ready bit is set when turning
on the drive if the DC bus is not ready.
Hex Value:
0040H
Sug. Var. Name:
IC_BUS@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
The bus is ready when the DC bus voltage is greater than the undervoltage
threshold value stored in local tunable UVT_E0% and has reached a steady state,
and feedback indicates that the pre-charge contactor has closed.
This interlock bit will also be set when turning on the drive if the bus enable bit
(register 100/1100, bit 4) has not been set. Refer to the SA3100 Power Modules
instruction manual (S-3058) for more information about internal DC bus control.