Appendix b, Ppendix, Sa3100 volts / hertz regulator register reference – Rockwell Automation SA3100 Distributed Power System Drv Config,Program User Manual
Page 119
SA3100 Volts / Hertz Regulator Register Reference
B-1
A
PPENDIX
B
SA3100 Volts / Hertz Regulator
Register Reference
REGISTER MAP
Registers
Function
0-23
Flex I/O port registers
24-79
System Use Only
80-89
UDC/PMI comm. status registers for drive A
90-99
System Use Only
100-106
Command registers for drive A
107-199
System Use Only
200-222
Feedback registers for drive A
223-299
System Use Only
300-599
Application registers updated every scan
for drives A and B
600-999
System Use Only
1000
UDC module test switch register
1001-1017
UDC module meter port setup registers
1018-1079
System Use Only
1080-1089
UDC/PMI comm. status registers for drive B
1090-1099
System Use Only
1100-1106
Command registers for drive B
1107-1199
System Use Only
1200-1222
Feedback registers for drive B
1223-1299
System Use Only
1300-1599
Application registers updated every scan
for drives A and B
1600-1999
System Use Only
2000-2010
Interrupt Status and Control registers for
drives A and B
2011-2047
System Use Only
REGISTER/BIT DESCRIPTIONS
FLEX I/O PORT REGISTERS
A / B
0 / 12
PMI Module 0, Digital I/O
1 / 13
PMI Module 1, Digital I/O
2 / 14
PMI Module 2, Digital or Analog I/O
3 / 15
PMI Module 2, Analog 1 I/O
4 / 16
PMI Module 2, Analog 2 I/O
5 / 17
PMI Module 2, Analog 3 I/O
6 / 18
PMI Module 2, Analog 4 I/O
7 / 19
PMI Module 2, Analog 5 I/O
8 / 20
PMI Module 2, Analog 6 Input
9 / 21
PMI Module 2, Analog 7 Input
10 / 22
Flex System Fault Bits, PMI Module 0 & 1 Faults
Bit
0 Flex Bus Fault
1 Flex Clock Fault
2 Flex Scratch Pad Fault
3 Flex Dual Port Fault
4 - 7 Not Used
8 Module 0 Not Plugged In
9 Module 0 Communication Error
10 Module 0 Bad ID
11 Module 0 Location Error
12 Module 1 Not Plugged In
13 Module 1 Communication Error
14 Module 1 Bad ID
15 Module 1 Location Error
FLEX I/O PORT REGISTERS (CONTINUED)
11 / 23
Flex Module 2 Fault Bits
Bit
0 Module 2 not plugged in
1 Module 2 communication error
2 Module 2 Bad ID code
3 - 7 Not Used
8 Channel 0 output open/input underrange
9 Channel 1 output open/input underrange
10 Channel 2 output open/input underrange
11 Channel 3 output open/input underrange
12 Channel 4 output open/input underrange
13 Channel 5 output open/input underrange
14 Channel 6 output open/input underrange
15 Channel 7 output open/input underrange
UDC-PMI COMMUNICATION STATUS
A/B
80 /1080 UDC Module port status
Bit
0 Invalid rcr interrupt
1 No end of frame status
2 CRC/framing error
3 Overrun error
4 DMA format error
5 Transmitter underrun
6 CCLK comm sync error
7 Loopback data error
8 Missed gains
9 Multiplexed data verification error
10 No matching PMI OS
11 Invalid PMI OS header
12 Incompatible PMI H/W
81 /1081 UDC module good msg. recvd. count
82 /1082 UDC module CRC error count
83 /1083 UDC module format error count
84 /1084 PMI port status
Bit
0 Invalid rcr interrupt
1 No end of frame status
2 CRC/framing error
3 Overrun error
4 DMA format error
5 Transmitter underrun
6 CCLK comm sync error
8 UDC CCLK comm sync error
9 Multiplexed data verification error
12 Invalid PMI start OS address
13 Insuff. PMI memory to load PMI OS
14 Invalid PMI load address
15 PMI OS overflow
85 /1085 PMI good msg. recvd. count
86 /1086 PMI CRC error count
87 /1087 PMI format error count
88 /1088 Comm/link status
89 /1089 UDC transmitted msg. count
COMMAND REGISTERS
A/B
100/1100 Drive Control
Bit
0 Enable PMI loop
PMI_RUN@
1 Enable tuning
PMI_TUN@
2 Bridge test enable
BRG_TST@
4 Bus enable
BUS_ENA@
5 DC braking on
BRK_ON@
7 Synch transfer request
1
SYN_REQ@
8 Fault reset
FLT_RST@
9 Warning reset
WRN_RST@
15 UDC task running (status)*
UDC_RUN@
101/1101 I/O Control
Bit
2 External fault LED
EXT_LED@
4 Auxiliary output
AUX_OUT@
6 Enable resolver calibration
RES_CAL@
8 Enable external strobe
STR_ENA@
9 External strobe falling edge
STR_ENF@
10 STATOR_IZ_E1% tuning
TUN_IZ@
15 UDC module loopback test
UDC_LB@
102/1102 Frequency reference (high)
FRQ_REF(H)!
103/1103 Frequency reference (low)
FRQ_REF(L)!
104/1104 Boost voltage reference
VLT_REF%
Id reference (dual-wound motor) ID_REF%
105/1105 Bridge test code
TST_CODE%
106/1106 PMI D/A output
PMI_DA%
107/1107 Synchronous transfer volts
SX_V%
Vector orientation ref (dl-wnd mtr)VO_REF%
108/1108 DC braking reference
BRK_REF%
109/1109
FEEDBACK REGISTERS
A/B
200/1200 Drive status
Bit
0 Frequency control on
FRQ_ON@
1 Auto tuning complete
PMI_ATC@
2 Freq ref saturation plus
FRF_SP@
3 Freq refsaturation minus
FRF_SM@
4 DC bus ready
BUS_RDY@
7 OK to synch transfer
SYN_OK@
8 Fault detected
FLT@
9 Warning detected
WRN@
13 Flex I/O updated
(System use)
14 CCLK synchronized
CCLK_OK@
15 PMI OS loaded
PMI_OK@
201/1201 I/O status
Bit
0 Run permissive input
RPI@
1 M-contactor feedback
M_FDBK@
2 Auxiliary input 2
AUX_IN2@
3 Auxiliary input 3
AUX_IN3@
4 Auxiliary input 4
AUX_IN4@
5 Auxiliary input 5
AUX_IN5@
6 Resolver gain calibrated
RES_GAN@
7 Resolver balance calibrated
RES_BAL@
8 External strobe detected
STR_DET@
9 External strobe level
STR_LVL@
10 Stator IZ tuning complete
TUNED_IZ@
1.
Feature reserved for future releases.