Publication DNET-UM003A-EN-P - August 2000
2-16 Construct Your Starter Kit
Set Node Address Switches for Channel 1
You must set the node address for the 1771-SDN before you install the
scanner and go online. To set the I/O chassis addressing node
switches:
1. Locate the switch bank labeled “Channel 1” on the left side of
the module.
The address range is from 0 to 63. It will be set to 63 from the
factory as shown in the illustration. All autobaud devices are
internally set to node 63. The node address for DeviceNet
Channel 1 must not conflict with the node address of any other
device on the network. For this demonstration, you want to set
the address to 0.
2. Use a ball point pen or a similar object to adjust switches 3
through 8 to match the illustration. All of the switches should be
in the off, in the 0 position.
Install Your Scanner
After you set the dip switches and with the chassis power off, insert
the 1771-SDN scanner into slot 2 of your PLC-5 processor chassis.
IMPORTANT
Do not use a lead pencil because the tip can break
off and jam or short out the switch.
Channel 1 DIP switches
On=1
Off=0
On=1
Off=0
8
set
from
factory
Node 63
on
1 2 3 4 5
6 7 8
Node 0
set for
SKITs
3 & 4
on
1 2 3 4 5
6 7 8
30292
IMPORTANT
Be certain to turn the power to your chassis off
before inserting your scanner.
IMPORTANT
Refer to installation instructions that come with your
1771-SDN for installation details.