Rockwell Automation T8094 8000 Series TMR System Safety Manual User Manual
Page 92
![background image](/manuals/581436/92/background.png)
SAFETY MANUAL
D oc N umber T8094
I ssue 27 – June 2013
Page 71 of 103
TÜV Certified
Configuration
Conditions
Digital Outputs
MDO32BNS, TMR,
24 VDC
MDO16GNS, TMR,
48VDC
MDO16FNS, TMR,
120VDC
MDO16CNS, TMR,
120VAC
Internal 2oo3
(2oo3 implemented in
a single module)
Normally energized (de-energize to trip): certified
SIL 3.
Normally de-energized (energize to trip): certified
only for applications that fulfil the requirements
under section 3.2.4.
May be used in single module or active/standby
configurations.
Analogue Output
MAO04NND, TMR,
0-22mA
Not safety related but
interference free
Certified as non-interfering and can be used for non-
safety-critical devices.
Table 15- Output Modules, Triguard I/O
TÜV Certified
Configuration
Conditions
Analogue Output /
Pulse Input
MHB44IND, TMR,
4-20mA,
1Hz-35KHz
Not safety related but
interference free
Certified as non-interfering and can be used for non-
safety-critical devices.
Table 16 – Triguard Multi-purpose Modules
Conditions
Controller Chassis
8100
Certified as safety related and can be used for safety critical
applications in SIL 3.
Primary,
Secondary
and
Remote Triguard Chassis
Certified as safety related and can be used for safety critical
applications in SIL 3.
Power Supplies
PAC, PDC
Certified as safety related and can be used for safety critical
applications in SIL 3.
Table 17 – Auxiliary Chassis and PSUs