beautypg.com

1 safety-related configurations – Rockwell Automation T8094 8000 Series TMR System Safety Manual User Manual

Page 40

background image

SAFETY MANUAL

D oc N umber T8094
I ssue 27 – June 2013

Page 19 of 103

3.2.1 Safety-Related Configurations

TÜV Certified

Configuration

Conditions

TMR Processor

8110

2oo3

Certified as safety-related and can be used for
safety-critical applications in SIL 3 in single module
or active/standby configurations.

TMR Processor

8110B (IRIG-B)

2oo3

Certified as safety-related and can be used for
safety-critical applications in SIL 3 in single module
or active/standby configurations.
IRIG-B functionality is interference free and can not
be used for safety functions

Peer to Peer

Software board
definitions

Dxpdi16,

Dxpdo16,
Dxpai16,
Dxpao16,
Dxpdi128,
Dxpdi128 &
dxpnc40

Certified for use over

a single

communication

network or multiple

networks

Certified as safety-related and can be used for
safety-critical communication in SIL 3 applications.

Peer to Peer

Software board
definitions

Dxpai128 &
Dxpao128

Certified for use over

a single

communication

network or multiple

networks

Certified as safety-related and can be used for
safety-critical communication in SIL 3 applications
provided two separate

Dxpai128 & Dxpao128

board definitions are used for safety values, the
safety values from the two Dxpai128 boards (or
digital trip points from the values) shall have a
1oo2 vote within the receiving application.

TMR Interface

8160

2oo3

Certified as safety-related and can be used for
safety-critical applications in single module or

active/standby configurations.

Communication
Interface

8150 / 8151 / 8151B

Not safety related but

interference free

Certified as non-interfering safety-related and can
be used for safety-critical communication in SIL 3 as
part of the grey channel in single or dual module
configurations.

Expander Modules,
(XIM / XPM)

8310 / 8311

Not safety related but

interference free

2oo3

Certified as non-interfering safety-related and can
be used for safety-critical communication in SIL 3 as
part of the grey channel in single module or
active/standby configurations.

Fiber TX/RX Unit

8314

Not safety related but

interference free

2oo3

Certified as non-interfering safety-related and can
be used for safety-critical communication in SIL 3.

Table 2 - Central Modules