When End-Users See Updates
When you change or replace a Display Document on your Web site, users
do not see this change until the previously downloaded Display Document
expires in their cache. See Expiration of Displays (page 34) for details.
There is no automated way for a developer to refresh the displays that are
cached on each user's PC.
Work with Element Relative Displays
Displays can reference points that vary based on their context, as defined
using element Relative Displays. In FactoryTalk Historian ActiveView, the
window used to select a different element in FactoryTalk Historian
ProcessBook is not available. Use other programmatic means to change the
context.
Configuration
The acview.ini file contains configuration and preference settings for
FactoryTalk Historian ActiveView (similar to the procbook.ini used
for FactoryTalk Historian ProcessBook, and identical in format). This file
resides in the pipc\Dat directory. The significant keywords are:
Keyword
Section(s)
Description
ToolbarVisibility
Startup
Specifies whether the toolbar is visible. When set
to 1, the toolbar is visible, when set to 0 (zero), it
is hidden. When a user turns the toolbar on or
off, this setting updates automatically.
Show Value
Attributes
Startup
Specifies whether value attribute flag icons
appear. When set to 1, (the default) value
attributes appear. When set to 0, value attribute