beautypg.com

Trustedtm board definitions, Process historian, Sequence of events – Rockwell Automation T8082 Trusted Toolset Suite User Manual

Page 64: Trusted, Board definitions, Table 5 oem parameters

background image

Trusted

TM

Toolset Suite T8082

Issue 14 Feb 10

PD-T8082

64

4. Trusted

TM

Board Definitions

Details of complex I/O equipment definitions are given in the appropriate I/O module or interface/bridge
module PD. These define the data exchanged between the system and application in relation to a
particular module. Each module in the system needs an entry in the I/O Connection Editor, as
described in section 3 above. The definitions given in this section are for single board definitions, used
for non-module related tasks.

4.1. Process Historian

Description:

Process Historian with selectable Delta capture

OEM PARAMETERS:

OEM parameter

Valid
numbers

Description

DELTA

1 – any

The change in the variable that is needed from the last
scan to log the variable to the process historian collector.

BANK

1 – 32

There are 32 banks. These all contain a maximum of 100
analogue variables

Table 5 OEM Parameters

PARAMETERS

BOARD_ID

7000

DELTA

100

BANK

1

4.2. Sequence of Events

Description: Sequence of Events (SOE). Any variable connected to a channel of this board will be
stored in the SOE buffer on the Trusted

TM

Communications Interface. The board has the facility for up

to 100 variables.

OEM PARAMETERS:

None