Compliance with Electromagnetic Compatibility Standards
C-5
* See figure C.2 for mounting dimensions.
C.3.2 Installing AC Mains Filters in GV3000/SE Drives M/N 50T41xx and
75T41xx
In GV3000/SE drives M/N 50T41xx and 75T41xx, the AC Mains Filters are installed
within the GV3000/SE chassis at the factory. No additional filter installation is required.
Continue with section C.4.
C.3.3 Installing AC Mains Filter M/N 2DF4125
GV3000/SE drive M/N 125R41xx and AC Mains Filter M/N 2DF4125 are to be
mounted separately. See figure C.2. They must be mounted on a steel surface with
good conductivity between the two assemblies, for example, the mounting surfaces
should not be painted.
When placing the drive and the AC Mains Filter in a cabinet or IP20 enclosure, a
common ground bus bar is to be located in front of the terminals. This bus bar must be
solidly connected to the back panel to ensure good conductivity. All cable screens
must be connected to this bus bar. To ensure good conductivity, use galvanized cable
brackets to connect the screens to the bus bar.
Continue with section C.4.
Table C.2 – AC Mains Filter Mounting Dimensions and Weight
Dimension
AC
Mains
Filter
2DF4283
AC
Mains
Filter
2DF4284
AC
Mains
Filter
2DF4285
AC
Mains
Filter
2DF4286
AC
Mains
Filter
2DF4125
A
217 mm
8.5"
272 mm
10.7"
272 mm
10.7"
365.5 mm
14.3"
*
B
387mm
5.25"
441 mm
17.4"
575 mm
22.6"
958 mm
37.7"
*
C
362 mm
14.25"
415 mm
16.3"
550 mm
21.7"
933 mm
36.7"
*
D
174 mm
6.9"
230 mm
9.1"
232 mm
9.1"
300 mm
11.8"
*
E
9 mm
0.35"
9 mm
0.35"
9 mm
0.35"
11 mm
0.43"
*
F
21.5 mm
0.85"
21 mm
0.83"
20 mm
0.79"
_
*
G
53 mm
2.1"
53 mm
2.1"
93 mm
3.7"
91.5 mm
3.6"
*
H
180 mm
7.1"
231 mm
9.1"
235 mm
9.25"
181 mm
7.1"
*
J
18 mm
0.71"
18 mm
0.71"
43 mm
1.7"
35 mm
1.4"
*
K
22 mm
0.87"
22 mm
0.87"
28 mm
1.1"
43 mm
1.7"
*
Filter
Weight
3.2 kg
7 lbs
3.2 kg
7 lbs
5 kg
11 lbs
20 kg
44 lbs
48 kg
105 lbs