Rockwell Automation GV3000/SE AC Drive Ver. 6.06 Hdwe Ref., Installation, and Troubleshooting Manual User Manual
Page 105
Technical Specifications
A-3
)
*These are the maximum times from transitioning the input to the drive reacting to the input.
Table A.6 – Encoder Feedback Device Specifications (FVC Regulation Only)
Specification
Rating
Motor Poles
2, 4, 6, or 8 poles
Overcurrent IET
200% load (based on drive nameplate
rating)
Overload Current Rating
150% for 1 minute (based on drive
nameplate rating)
Speed Control Range
1:600 with 1024 PPR
Speed Control Response
15 Hz (typical)
Encoder Feedback
15 V differential quadrature, encoder
incremental (512 PPR, 1024 PPR, 2048
PPR, 4096 PPR)
Service Factor
1.0
Table A.7 – Input Signal Response Times (Maximum)
Signal Type and Source
Volts/Hertz Regulation*
Vector Regulation*
Keypad START
150 milliseconds
130 milliseconds
Terminal Strip:
START
126 milliseconds
105 milliseconds
STOP, RESET, FL
75 milliseconds
75 milliseconds
Preset Speeds
75 milliseconds
75 milliseconds
Analog Speed/Trim
Reference
16 milliseconds
5 milliseconds
Analog Torque
Reference
N/A
0.5 milliseconds
Network:
START
46 milliseconds + network
transport time
25 milliseconds + network
transport time
STOP, RESET, FL
26 milliseconds + network
transport time
25 milliseconds + network
transport time
Analog Speed/Trim
Reference
5 milliseconds +
network transport time
5 milliseconds +
network transport time
Torque Reference
N/A
0.5 milliseconds +network
transport time