Standard input/output connection points, Table 31, Table 32 on – Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Installation Instructions User Manual
Page 89

Rockwell Automation Publication 6000-IN006A-EN-P - April 2014
89
Power Cabling and Control Signal Wiring Details
Appendix F
Standard Input/Output
Connection Points
Table 31 - I/O Connections related to High Voltage Cabinet
Serial Number
Name of I/O Connection
AI
AO
DI
DO
Note
1
Input circuit breaker closing node is allowed
(917, 918)
1
Serially connected into the input circuit breaker's closing circuit (the VFD
provides passive normally open points, valid when closed)
2
Trip connection points within the VFD
(919, 920)
1
Can be connected into input circuit breaker's closing circuit in parallel (the VFD
provides passive normally open points, valid when closed)
3
Input circuit breaker already closed
connection point (117, 119)
1
Circuit breaker's auxiliary normally open connection points (valid when closed)
Table 32 - I/O Connections related to Remote Distributed Control System
Serial Number
Name of I/O Connection
AI
AO
DI
DO
Note
1
VFD speed regulation command (931, 402)
1
User-provided 4...20mA
Spare (932, 402)
1
User-provided 4...20 mA (spare)
Spare (934, 402)
1
User-provided 4...20 mA (spare)
Spare
1
User-provided 4...20 mA (spare)
2
VFD speed feedback signal (927, 928)
1
VFD-provided 4...20mA
3
VFD current feedback signal (925, 926)
1
VFD-provided 4...20mA
4
Alternate start command signal (431, 401)
1
User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)
Remote DCS start command signal (449,
401)
1
User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)
5
Alternate stop command signal (432, 401)
1
User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)
Remote DCS stop command signal (450, 401)
1
User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)
6
Spare (433, 401)
1
User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)
7
Spare (434, 401)
1
User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)
8
Spare (435, 401)
1
User-provided normally open passive dry contact (switch quantity)
Spare (436, 401)
1
User-provided normally open passive dry contact (switch quantity)
Spare (437, 401)
1
User-provided normally open passive dry contact (switch quantity)
Spare (438, 401)
1
User-provided normally open passive dry contact (switch quantity)
9
Remote DCS alternate (448, 401)
1
User-provided normally open passive dry contact (switch quantity)
10
Remote DCS fault reset command (412, 401)
1
User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)
Alternate reset command (412, 401)
1
User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)
11
Emergency stop button command
(1101, 1102)
1
User-provided normally closed passive dry contact
(voltage class higher than 220V AC, 5 A, switch quantity)
12
VFD allow closing indication (901, 902)
1
VFD-provided normally open passive dry contact
(voltage class ≤220V AC, 5 A) (used for Remote DCS)
Circuit breaker closing indication (903, 904)
1
VFD-provided normally open passive dry contact
(voltage class ≤220V AC, 5A) (used for Remote DCS)