beautypg.com

Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Installation Instructions User Manual

Page 30

background image

30

Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

Chapter 2

Drive Mechanical Installation

3.

Secure the cabinets together using M8 hardware. See

Torque

Requirements on page 71

for proper torque requirements.

Open the doors to access front edge joining holes (5 places).

4.

Remove all back plates to access rear edge joining holes (5 places).

Secure with M8
hardware (10 places)

M8x25 Hex Bolt

Lock Washer

M8 Hex Nut

Flat Washer (x2)

Cabinet Sidesheets

TIP

Each back plate will have two keyhole screw holes on either side. Remove all of
the other screws first. Loosen the two screws in the keyhole screw holes last
and lift the back plate to remove. Do not remove these screws.

Do not replace the back plates until the Drive Electrical Interconnection Process
is complete (See

Drive Electrical Interconnection on page 55

).

To replace the back plates, the two remaining screws orient and hold the back
plate in place while fastening the other screws holding the back plates to the
frame of the cabinet. Tighten these screws last to complete the process.