Publication 6185-UM006A-EN-P - July 2002
D-2 Product Specifications
Operator Input
6185-F
Optional resistive anti-glare touchscreen with serial
RS-232 interface controller
Electrical
6185-F
Line Voltage
90 to 254VAC
Line Frequency
50-60Hz
Ground Leakage
1.0
µ
A max. at 1.5KVDC
Power Consumption
30W max.
Environmental
6185-F
Panel Mount Rating
NEMA Types 1/12/4X (indoor use only)
(built to IP65 or IP53 standards)
Relative Humidity
10% to 90% non-condensing
Temperature
(1)
(2)
Operating
Storage
0° to 50°C
-20° to 60°C
Electrostatic Discharge
Operating
Storage
8.0K VDC (IEC 801-2, level 3)
15.0K VDC
Shock
(Operating and Storage)
20g (1/2 sine, 11msec)
Vibration
(Operating and Storage)
0.015in p-p, 10-53Hz
2.0 G’s peak, 53-640Hz sine
(1)
At 40°C operating temperature, humidity should never exceed 90%. At 50°C, humidity should never
exceed 50%. Operating the RAC6185 Industrial Flat Panel Monitor (6185-F) beyond these limits for
extended periods of time can reduce the life of the product. See Figure 2.1 on page 2-3 for additional
information.
(2)
Above 45°C operating temperature, display brightness should never exceed 50%. Operating the
RAC6185 Industrial Flat Panel Monitor (6185-F) beyond these limits for extended periods of time can
reduce the life of the product. Consult the factory for additional information.
Physical
6185-F
Front Panel Dimensions
(WxHxD)
17.250 in x 13.969 in x 0.300 in
(438.15mm x 354.81mm x 7mm)
(without rack adapters)
Rear Chassis Dimensions
(WxHxD)
15.584 in x 11.896 in x 2.310 in
(395.83mm x 302.16mm x 58.67mm)
Net Weight
12.0 lbs (5.4 kg)
Shipping Weight
24.0 lbs (10.9 kg)