4.6

Restrictions on Use

The channels on a Voltage Input module in an AutoMax/DCS 5000

system are to be configured from only one application task.
Do not configure a channel on the Voltage Input module unless a

transmitter or transducer is connected to that channel. If you do, the

result will be an outĆofĆrange condition.
If the Voltage Input module is in an AutoMate remote rack, both the

master Remote I/O Processor and the slave Remote I/O Processor

must be M/N 45C201B or later. If either Processor is of an earlier

version, the remote rack will not stay onĆline with the master.
You can place up to 15 Voltage Input modules in either a local or

remote AutoMate rack when using a 50 Amp AutoMate Power Supply

(M/N 45C322). When using a 20 Amp AutoMate Power Supply (M/N

45C321) you are limited to:
D 8 Voltage Input modules in a local rack with an AutoMate 30

Processor

D 5 Voltage Input modules in a local rack with an AutoMate 40

Processor

D 10 Voltage Input modules in a remote rack with a Remote I/O

Processor.

You can place up to 15 Voltage Input modules in a local AutoMax

rack. You can place up to five Voltage Input modules in a remote

AutoMax rack due to register transfer limitations. For additional

information refer to the AutoMax Remote I/O Communications

Manual (JĆ3606).
Note that when Voltage Input modules are placed in an AutoMax

remote rack:
D the powerĆup default values in registers 23 to 31 are reset to zero.

You must individually enter new values into these registers.

D the Read Channel Configuration command (register 31, bits 12 to

15) will not update registers 24 to 31 and therefore cannot be

used in a remote installation.