4Ć22

Register 3005= Register contains the voltage input channel's High

High alarm value. This value is provided by the data

table in the 5000Ćseries registers.

Register 3006= Register contains the voltage input channel's High

alarm value. This value is provided by the data table

in the 5000Ćseries registers.

Register 3007= Register contains the voltage input channel's Low

alarm value. This value is provided by the data table

in the 5000Ćseries registers.

Register 3010= Register contains the voltage input channel's Low

Low alarm value. This value is provided by the data

table in the 5000Ćseries registers.

Register 3011= Register contains the voltage input channel's

configuration command. This value is provided by

the data table in the 5000Ćseries registers.

Registers 3100 to 3137= Registers contain the data read from the

Voltage Input module.

Registers 5000 to 5027= Registers contain the data used to

configure the voltage input channels. Each

channel uses eight registers:

Max.

Min.

Average

High

Low

Configure

Max.

Scale

Min.

Scale

Average

Samples

High

High

High Low

Low

Low

Configure

Command

Reg. 5000 = 2000 -100

20

1800

1600

400

0

12800*

Reg. 5010 = 3000

0

20

2500

2000

500

250

12800ă

Reg. 5020 =10000

0

20

9000

7500 2500 1000

12800ă

*12800=3200 Hex

Note that you must use the POINT MONITOR function to enter these

values into the 5000Ćseries registers before you begin executing the

program.
Register 5200= Register contains the value (0) for the READY

command.