4Ć22
Register 3005= Register contains the voltage input channel's High
High alarm value. This value is provided by the data
table in the 5000Ćseries registers.
Register 3006= Register contains the voltage input channel's High
alarm value. This value is provided by the data table
in the 5000Ćseries registers.
Register 3007= Register contains the voltage input channel's Low
alarm value. This value is provided by the data table
in the 5000Ćseries registers.
Register 3010= Register contains the voltage input channel's Low
Low alarm value. This value is provided by the data
table in the 5000Ćseries registers.
Register 3011= Register contains the voltage input channel's
configuration command. This value is provided by
the data table in the 5000Ćseries registers.
Registers 3100 to 3137= Registers contain the data read from the
Voltage Input module.
Registers 5000 to 5027= Registers contain the data used to
configure the voltage input channels. Each
channel uses eight registers:
Max.
Min.
Average
High
Low
Configure
Max.
Scale
Min.
Scale
Average
Samples
High
High
High Low
Low
Low
Configure
Command
Reg. 5000 = 2000 -100
20
1800
1600
400
0
12800*
Reg. 5010 = 3000
0
20
2500
2000
500
250
12800ă
Reg. 5020 =10000
0
20
9000
7500 2500 1000
12800ă
*12800=3200 Hex
Note that you must use the POINT MONITOR function to enter these
values into the 5000Ćseries registers before you begin executing the
program.
Register 5200= Register contains the value (0) for the READY
command.