5Ć2

DANGER

VOLTAGE IS PRESENT ON THE PLUG CONNECTOR TERMINALS. DISCONNECT

THE POWER AT THE SOURCE BEFORE TOUCHING THE PLUG CONNECTOR

TERMINALS. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN

SEVERE BODILYINJURYOR LOSS OF LIFE.

DANGER

DO NOT TOUCH THE CONNECTORS ON THE FACEPLATE IF THERE IS POWER

ON THE WIRES ATTACHED TO THE PLUG CONNECTOR SCREW TERMINALS.

ALWAYS TURN OFF POWER BEFORE HANDLING A CONNECTOR THAT IS

WIRED. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE

BODILYINJURYOR LOSS OF LIFE.

Step 2.

Turn off power to the module. Verify that the input power

connector is connected securely to the faceplate. Verify

that the I/O Rail cable connections are tight at both ends.

Step 3.

Turn on power to the module. If the LEDs are still off, try

replacingthe I/O Rail cable. Check that the input

connector pins are not bent.

Step 4.

If the LEDs are still off, turn off power to the module and

replace the power supply fuse on the front panel following

the directions below.

CAUTION

MAKE CERTAIN THAT THE ANALOG RAIL MODULE CONTAINS THE PROPER

FUSE FOR THE POWER SUPPLYBEING USED. USE A .25 A FUSE FOR 120 VAC

POWER AND A .75A FUSE FOR 24 VDC POWER. FAILURE TO OBSERVE THIS

PRECAUTION COULD RESULT IN DAMAGE TO OR DESTRUCTION OF THE

EQUIPMENT.

a) Use a screwdriver to release the fuse holder located on

the AnalogRail module faceplate. Pull the fuse holder

out of the module.

b) Take the old fuse out of the fuse holder and replace it

with the new fuse. Use a .25A fuse for 120 VAC power

and a .75A fuse for 24 VDC power. See Appendix A for

the fuse type and rating.

c) ReĆinsert the fuse holder into the module. Turn the

screwdriver clockwise while pressingdown on the fuse

holder. The fuse holder must be flush against the

faceplate.

Step 5.

Turn on power to the module. If both LEDs still do not