Rockwell Automation 61C346 4 Input 0-10V Analog Rail Module User Manual
Page 21
![background image](/manuals/580022/21/background.png)
3Ć7
Step 13. Set the Mode" switch on the faceplate of the module to
the desired position.
Step 14. Connect the I/O Rail cable between the Analog Rail
connection labeled Input" and any rail connector on the
Reliance device that will communicate with the module.
Turn on power to the Reliance device connected to the
module. Recall that the Mode switch is read each time the
Reliance device connected to the Analog Rail module is
powered up. If applicable, reĆconnect the cable between
the Local I/O Head, or the DCS/AutoMax Remote I/O
Head, and the host.
Step 15. Turn on power to the Analog Rail module Input Power"
connections.
Step 16. Turn on power to the external hardware connected to the
Analog Rail module.
Step 17. Verify that the hardware has been installed correctly.
For AutoMate systems, use the APX Point Monitor function
to test the module. To test the input channels, verify that
the input signal in the channel (0 to 10V) is proportional to
a voltmeter reading at the terminal points.
For DCS 5000, AutoMax, or Distributed Power DĆC Power
systems, use the DCS 5000 or AutoMax Programming
Executive software I/O Monitor function, respectively. To
test the input channels, verify that the input signal in the
channel (0 to 10V) is proportional to a voltmeter reading at
the terminal points.