3.0 INSTALLATION

This section describes how to install and replace the Analog Rail

module. Note that analog signals are sensitive to variations in

temperature. The Analog Rail module is designed to perform

optimally at room temperature, approximately 25

o

C. In all cases, the

ambient temperature of the installation must be maintained in the

range specified in Appendix A to ensure the highest possible

accuracy.

DANGER

THE USER IS RESPONSIBLE FOR CONFORMING WITH THE NATIONAL

ELECTRICAL CODE AND ALL OTHER APPLICABLE LOCAL CODES. WIRING

PRACTICES,

GROUNDING,

DISCONNECTS,

AND

OVERĆCURRENT

PROTECTION ARE OF PARTICULAR IMPORTANCE. FAILURE TO OBSERVE

THIS PRECAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF

LIFE.

DANGER

DO NOT TOUCH THE CONNECTORS ON THE FACEPLATE IF THERE IS

POWER ON THE WIRES ATTACHED TO THE PLUG CONNECTOR SCREW

TERMINALS. ALWAYS TURN OFF POWER BEFORE HANDLING A

CONNECTOR THAT IS WIRED. FAILURE TO OBSERVE THIS PRECAUTION

COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.

CAUTION

THE ANALOG RAIL MODULE IS DESIGNED TO BE POWERED BY EITHER 24

VDC OR 120 VAC. CONNECT THE PROPER POWER SOURCE TO THE

MODULE. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN

DAMAGE TO OR DESTRUCTION OF THE EQUIPMENT.

3.1

Wiring

To reduce the possibility of electrical noise interfering with the proper

operation of the control system, exercise care when installing the

wiring between the module and the external hardware.
Use shielded twisted pair for all wiring between the Analog Rail

module and the external hardware. Beldent 8761 or an equivalent

cable type is recommended. Cable lengths should be limited to 50

feet maximum. For detailed recommendations refer to IEEE 518.