Initial Installation

Use the following procedure to install the Analog Rail module.
Step 1.

Using the mounting dimensions shown in figure 3.1,

prepare the necessary mounting provisions on the panel.

The module is designed to be mounted vertically using

four #10 or M5 bolts or studs. Multiple modules should be

mounted side by side. The flange width of two modules

side by side is sufficient to dissipate the heat produced by

the modules. The modules can also be mounted one

above the other, but since this hardware configuration

does not allow the most efficient heat dissipation, the

minimum clearance between the module chassis is 3".

See figure 3.1.

Depth: 7.75"

Diameter of mounting holes: 7/32"

7.0"

2.44"

3.0"

2.94"

9.25"

Figure 3.1 ĆMounting Dimensions