3Ć5

Channel 0

Channel 1

Channel 2

Channel 3

Common

1

2

3

Common

4

5

6

+

-

I

Source

VĆIn

Common

7

8

9

+

-

I

Source

VĆIn

Common

10

11

12

+

-

I

Source

VĆIn

+

-

I

Source

VĆIn

Figure 3.2 ĆTypical Recommended Input Shielding Methods

Step 11. Turn off power to the Reliance device that will be

connected to the Analog Rail module.

Step 12. Set the Mode" switch on the faceplate of the module to

the desired position.

Step 13. Connect the I/O Rail cable between the Analog Rail

connection labeled Input" and an I/O port on the

Reliance device that will communicate with the module.

Turn on power to the Reliance device that will

communicate with the module. Recall that the Mode

switch is read each time the Reliance device connected to

the Analog Rail module is powered up.

Step 14. The Analog Rail installation is now ready for testing.

Inspect all work to assure that the installation has been

performed properly.

Step 15. Turn on power to the Input Power" wiring. Turn on power

to the external hardware. See Appendix A for power

supply specifications.

Step 16. Verify that the hardware has been installed correctly.

Before testing, insure that the external hardware will not

respond to output signals from the Analog Rail module.