0 programming, 1 analog rail module in automate systems – Rockwell Automation 61C346 4 Input 0-10V Analog Rail Module User Manual
Page 23
4Ć1
4.0 PROGRAMMING
This section describes how the data is organized in the module and
provides examples of how the module is accessed by application
programs.
When creating application programs, the programmer should
estimate the magnitude of input signals because they must be in the
specified range of the Analog Rail module (0Ć10V). Input signals
greater than 10V will be clamped at 4095. Input signals greater than
approximately 11.3V will also cause the overĆrange bit (12 decimal;
14 octal) to be set to 1. Signals less than 0V are clamped at zero (0).
Signals less than approximately -1V will also cause the underĆrange
bit (13 decimal; 15 octal) to be set to 1. See figure 4.1.
Counts
4095
0
<-1 = underĆrange
>11.3 = overĆrange
Volts
1 2 3 4 5 6 7 8 9 10
-1
11
Figure 4.1 Ć Input Signal Conversion
4.1
Analog Rail Module in AutoMate Systems
This section describes how the Analog Rail is used with AutoMate
systems. Local Head mode allows all four channels on the module to
be updated at the end of the scan (normal I/O update rate in this
configuration), or during the scan using AIN blocks (see section
4.1.4). Rail mode allows only one channel to be updated at the end
of the scan (normal I/O update rate in this configuration), or all four
channels to be updated during the scan if AIN blocks are used.