beautypg.com

Rockwell Automation 61C346 4 Input 0-10V Analog Rail Module User Manual

Page 30

background image

4Ć8

4.1.3

AutoMate Programming in Local Head Mode

In Local Head mode, the module is imaged in four I/O registers of the

processor. Data from all four channels is always available and will be

updated at the end of each scan. It is not necessary to select the

channel. After the I/O update, the register contains the data in the

format shown in figure 4.8.

17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

Octal

12 bits of converted analog data
overĆrange (1=overĆrange)
underĆrange (1=underĆrange)
not used

not used

Figure 4.8 ĆLocal Head Register Image for Input Channels

The Analog Rail module data may also be accessed in the middle of

the scan (as opposed to the end of the scan) using the appropriate

number of Analog In (AIN) blocks. The AIN block will set the

overĆrange or underĆrange bits if applicable. See section 4.1.4 for

more information about the AIN block.
Note that the AIN block is supported by the AutoMate 20E

M/N 45C224 and 45C225, but not the AutoMate 20 (M/N 45C20,

45C21, 45C220, 45C221) by APX Version 3.0.
For processors that do not support the AIN block, you can use the

MOVE block to move data in and out of the registers assigned.

OverĆrange and underĆrange bits should be used as inputs to error

coils. The I/O update will occur automatically at the end of each scan.

See Appendix C for a sample AutoMate program that reads from the

Analog Rail module without using the AIN block.