A. controlflash software error codes, Introduction, Controlflash software error codes – Rockwell Automation ControlFLASH Firmware Upgrade Kit User Manual User Manual
Page 41: Appendix

Rockwell Automation Publication 1756-UM105E-EN-E - October 2012
41
Appendix
A
ControlFLASH Software Error Codes
Introduction
This appendix describes common error messages you may see when running the
ControlFLASH software.
Error Message
Description
Log Viewer Error The event log viewer
(Notepad.exe) could not be found
Verify that the Notepad application is installed on your system.
Catalog Registry Error
The catalog registry database could not be read. Check with your technical
support representative to verify that the correct database is loaded.
Load Driver Error
The ControlFLASH software could not find an essential support file for the
selected catalog number. Check with your technical support representative
to verify that the correct drivers is loaded.
Invalid Catalog Number
The catalog number of the target device you selected does not match the
catalog number selected in the Catalog Number dialog box.
You selected an incorrect target device or catalog number. Select a device
that matches the catalog number or a different catalog number
Catalog Directory Error
The catalog directory database could not be read. Check with a technical
support representative to verify that the correct catalog database has been
loaded.
Invalid Revision
The upgrade revision selected is not compatible with the selected target
device. The selected firmware revision is either:
• older than the firmware currently on the target device.
• incompatible with the revision level of the target device.
ATTENTION: Do not continue with the upgrade until you have verified that
the upgrade is compatible with the selected device. Unpredictable system
operation could result.
Instance Validation Error
The target device did not report enough information to be properly
identified. Check with a technical support representative for help in
resolving this problem.
Script File Error
The script file associated with the selected upgrade is corrupt. Check with a
technical support representative to obtain a new script file.
Data File Error
The data file used in programming could not be read. Check with a technical
support representative to obtain a new data file.
Out of Memory Error
Your system is low on or out of RAM memory. The ControlFLASH software
could not allocate enough memory for data.
Free up RAM space by:
• Shutting down other applications currently running.
• Increasing the size of your virtual memory.
• Purchasing additional RAM, if necessary.