Rockwell Automation ControlFLASH Firmware Upgrade Kit User Manual User Manual
Page 32

32
Rockwell Automation Publication 1756-UM105E-EN-E - October 2012
Chapter 5 Use the Command Line
Entry
Description
Version
Version of the script file.
AbortOnFail
When flashing a device failed:
0 = continue flashing the remaining devices.
1 = stop flashing the remaining devices.
SkipOnFirmwareMatch
If a device to flash already has the matching firmware as stated in the script:
0 = do not skip flashing the device.
1 = skip flashing the device.
NumberDevices
Flash the first # of devices in this script file, begin with [Device1].
SilentMode
0 = ControlFLASH console window appears on screen and shows the flash progress.
1 = ControlFLASH console window does not appear on screen.
You will not receive any flash status feedback.
MultiFlash
0 = flash only one device at a time.
1 = flash up to five devices concurrently.
Catalog
Catalog number of device as registered with the current installed ControlFLASH software. To identify installed kits, refer to the GUI version of
ControlFLASH software.
For example: 1756-L63/A
Revision
Firmware revision you need to flash the device to. This revision must be registered for this device with the current install of the ControlFLASH
software. To identify installed kits, refer to the GUI revision of ControlFLASH software.
For example: 16.23
Path
FactoryTalk RSLinx path to the target device.
AB_PCIC-1 2 2 1 7
|_______| | | | |___Node address
| | | |_____Backplane
| | |__ ____PCICS Communication card address
| |________ControlNet cable address
|____________PCICS driver name
AB_ETH-2,192.168.1.4,1,7
|______| |_______| | |__Node Address
| | |___ Backplane
| |_________IP address
|________________ Ethernet driver name