6. Double-click the single ? on the Input Reference and select the

Controller Scoped tag, FFLD:0:I.In[1].SubStatus.

This function block will monitor the SubStatus of the AO
BKCAL_OUT for the Initialization Request.

7. Press .

8. Click the FFLD:0:I.In[1].SubStatus pin, then the SourceA pin to connect

them.

9. From the Move/Logical tab, click the Band button

and move the

Band block to the right of the Equal block.

10. Click the Output Reference button

.

The Output Reference is added to your sheet.

11. Drag and drop the Output Reference above the Band block.

12. Double-click the single ? on the Output Reference and select the

Controller Scoped tag, FFLD:0:O.Out[0].Initializing.

This function block will send the Initializing Acknowledge status to the
AO CAS_IN based on the status of the PIDE and the Initialization
Request.

13. Press .