Rockwell Automation 1757-FFLD Linking Device Configuration Manual User Manual

Page 134

background image

Publication 1757-PM002A-EN-E - June 2006

D-4 RSFieldbus Time Stamping Setup

3. Test the time stamping.

a. Place a transmitter's RESOURCES block in and out of service;

AUTO to OOS to AUTO.

b. The TIME_STAMP sub-parameter for the BLOCK_ALM

parameter should have a time stamp of when the RESOURCE block
went to OOS.

c. The TIME_STAMP sub-parameter for the UPDATE_EVT

parameter should have a time stamp of when the RESOURCE block
went to AUTO.