beautypg.com

Hardware requirements, Power supply, Power conditioner – Rockwell Automation 1757-FFLD Linking Device Configuration Manual User Manual

Page 12

background image

Publication 1757-PM002A-EN-E - June 2006

2-2 Set Up A System

Hardware Requirements

To build a simple fieldbus system, you need:

• Power supply

• Power conditioner

• Fieldbus cable

• Field devices

• Connector blocks

• Terminal blocks

• Terminators

• 1757- FFLD linking device

• Personal computer

Power Supply

The following power supplies are available according to the referenced
Fieldbus Foundation Physical Layer Profile Specification:

You can configure power supplies to provide dual redundancy as long as they
meet the IEC/ISA Physical Layer Standards requirements. It is not acceptable
for example, to merely parallel two power supplies.

A typical power supply for a small network is a SOLA SDN 5-24-100. 5A, 24
VDC output, 110 AC input. For more specifications on power supplies, see the
Power Considerations section on page 2-2.

Power Conditioner

A power supply impedance matching network is required for Fieldbus use.
This is referred to as a power conditioner. A power conditioner is a

Type 131 Non-I.S.

Power supply intended for feeding and I.S. barrier. Output
voltage depends on barrier rating.

Type 132 Non-I.S.

Power supply not intended for feeding and I.S. barrier.
Output voltage is 32 VDC Max.

Type 133 I.S.

Power supply; complies with recommended I.S.
parameters