beautypg.com

Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual

Page 63

background image

Publication 1756-UM528A-EN-P - April 2004

Using the Sequence of Events Module Features 5-11

In the example, a Sequence of Events module:

• is Enable CST Capture-enabled for all of its points
• uses a 2ms input filter setting for OFF to ON transitions

Three possible scenarios can result after an input transitioning from
OFF to ON in the given circumstances.

• Scenario #1 (no bounce) – The input turns ON and remains

for the full 2ms. In this case, the module considers the
transition valid and sends the data recorded at the transition
to the controller.

Figure 5.1

• Scenario #2 – The input turns ON but turns OFF before 2ms

(length of the input filter setting) elapses. In this case, the
Sequence of Events module continues to scan the input every
25

µs for 4x the length of the input filter setting (i.e., for 8ms).

At some point in those 8ms, the input turns ON again and
remains for at least 2ms (i.e., the input filter setting). In this
case, the module considers the transition valid and sends the
data timestamped at the original transition to the controller.

Figure 5.2

0

1

2

3

4

5

6

7

8

Input turns ON;
timestamp recorded

Time in milliseconds

Input remains ON for at least 2ms; transition is considered
valid and the timestamp is sent to the controller

43671

0

1

2

3

4

5

6

7

8

Time in milliseconds

Input turns ON and remains ON for at
least 2ms in the time period that is 4x the
input filter setting (i.e., 8ms).

The module sends the timestamp
recorded at the original transition point to
the controller.

Input turns OFF before
2ms have elapsed.

43672

Input turns ON;
timestamp recorded

This manual is related to the following products: