Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual
Page 113

Publication 1756-UM528A-EN-P - April 2004
Specifications and Module Block Diagrams A-3
EFT/B Immunity
IEC 61000-4-4:
±4kV at 2.5kHz on signal ports
Surge Transient
Immunity
IEC 61000-4-5:
±1kV line-line (DM) and ±2kV line-earth (CM) on signal
ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz
to 80MHz
Oscillatory Surge
Withstand
IEEE C37.90.1:
3kV
Enclosure Type Rating
None (open-style)
Agency Certification
(when product is marked)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CSA
CSA Certified Process Control Equipment for
Class I, Division 2 Group A,B,C,D Hazardous
Locations
FM
FM Approved Equipment for use in Class I
Division 2 Group A,B,C,D Hazardous Locations
CE
(3)
European Union 89/336/EEC EMC Directive,
compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick
(3)
Australian Radiocommunications Act,
compliant with:
AS/NZS CISPR 11; Industrial Emissions
EEx
(3)
European Union 94/9/EC ATEX Directive,
compliant with:
EN 50021; Potentially Explosive
Atmospheres, Protection "n" (Zone 2)
(1)
Maximum wire size will require extended housing - 1756-TBE.
(2)
Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1,
“Industrial Automation Wiring and Grounding Guidelines”.
(3)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other
certification details.