Installing the Sequence of Events Module 3-9
Recommendations for Using the Extended-Depth Housing
Consider the following recommendations when deciding to use an
extended-depth housing on your Sequence of Events module. It is
recommended you use the 1756-TBE when:
• using >36 18AWG wires
• using >23 14AWG wires
Cabinet Size Considerations With the Extended-Depth Housing
When you use an extended-depth housing (1756-TBE), the module
depth is increased. The diagram below shows the difference, in
terms of depth, between a Sequence of Events module using a
standard-depth housing and one using an extended-depth housing.
Figure 3.10
41682
Standard-Depth Housing
Extended-Depth Housing
144.73mm
(5.698in)
Rear Surface of
ControlLogix Chassis
131.75mm
(5.187in)
3.18mm (0.125in)
12.7mm
(0.5in)
IMPORTANT
The depth from front of the module to the back of
the chassis is as follows:
– standard-depth housing = 147.91mm (5.823in)
– extended-depth housing = 157.43mm (6.198in)