32 Configure Your FLEX I/O Module with RSLogix 5000 Software

6. On the Configuration tab, specify the following:

• Channel
• Frequency or Acceleration

If you choose Frequency, go to step 8. Go to step 9 if you choose
Acceleration.

7. For Frequency mode, specify the following:

• Maximum Frequency
• Frequency Range
• Minimum Frequency Sample Time

8. For Acceleration mode, specify the following:

• Maximum Frequency
• Frequency Range
• Minimum Frequency Sample Time
• Acceleration Calculation Time

9. Click the Alarms tab and specify the following:

• Missing Pulse Multiplier
• Missing Pulse Delay Multiplier
• Pulses to Terminate Sampling
• Wire-off/Missing Pulse Fault Select Mode

10. Click OK on the Module Properties dialog after you have configured the

different parameters.

The following options are available for each parameter on the Configuration
and Alarms tabs of the Module Properties dialog.