beautypg.com

Wiring connections for the frequency input module – Rockwell Automation 1794-IJ2XT FLEX I/O Frequency Input Modules User Manual User Manual

Page 33

background image

Publication 1794-6.5.11 - September 2011

Install Your FLEX I/O Frequency Input Module 23

Wiring Connections for the Frequency Input Module

Channel 0 Terminals

(5)

Channel 1 Terminals

(5)

Types of Inputs

Power Input RET

(7)

Power Input

RET

(7)

GND

(5)

Frequency

24V DC IEC1+ Proximity

(1)

(2)

7

6

3

8

9

12

24V DC Contact Switch

(3)

7

6

3

8

9

12

500mV AC Magnetic Pickup

7

(6)

5

3

8

10

12

50mV AC Magnetic Pickup

(4)

7

5

3

8

10

12

6V AC Vortex

2

1

3

13

14

12

3V AC Vortex

2

0

3

13

15

12

Gate

24V DC IEC1+ Proximity

(1) (2)

24

23

20

25

26

29

24V DC Contact Switch

(3)

24

23

20

25

26

29

500mV AC Magnetic Pickup

24

22

20

25

27

29

50mV AC Magnetic Pickup

(4)

24

22

20

25

27

29

(1)

As defined by standard IEC 1131-2.

(2)

RET not used on 2-wire devices.

(3)

Add external resistor from 24V to F or G for wire-off detection (0.4 mA) – (

50 K

Ω

).

(4)

Add a jumper between 50 mV and RET (Frequency – channel 0 = 3…4; channel 1 = 11…12)
(Gate – channel 0 = 21…20; channel 1 = 28…29).

(5)

Connect cable shields to GND terminals.

(6)

24V terminal may not be used on 2-wire magnetic devices.

(7)

All 4 RET terminals (ch 0 and 1, Freq, Gate) are internally connected together.

ATTENTION

Total current draw through the terminal base unit is limited to 10 A.
Separate power connections to the terminal base unit may be
necessary.