3-10 Communicate with the Interface Module

Slave-to-slave communication

Communicate with DH-485
Devices

DH-485 Token Passing Devices

The interface module operates as a token passing master on the
DH-485 network. It can communicate with other DH-485 master
stations (such as an SLC 5/02 processor) and with DH-485 token
passing slave devices (such as an SLC 5/01 processor).

The module communicates with other master stations using the
Allen-Bradley programmable controller command set. For details,
refer to the DF1 Protocol and Command Set Reference Manual,
publication 1770-RM516.

When the interface module is in

Slave-to-slave communication occurs

Local mode

Only if the module’s DF1 node is the same as the
DH-485 node for which the message is destined.
In this mode the RSLinx computer can only
communicate with one SLC node.

For example, if you want a DF1 slave terminal in
the illustration above to communicate with an
SLC processor in node 2 of the DH-485 network,
then the interface module’s DF1 slave address
must be set to 2.

Remote mode

Between the DF1 slave and any of the DH-485
devices connected to the interface module. The
addresses for the DH-485 devices are
determined by the group number in the interface
module.

Refer to the Half-duplex Remote Address
Conversion Table in Chapter 3.

For example, if the interface module in the
illustration above is configured as group 03, and
the DH-485 node to be accessed has a DH-485
address of 01, then the DF1 slave device will use
address 141 (octal) when accessing this device.

ATTENTION

Do not force outputs to a remote SLC system through
the interface module. Phone line disturbances,
interface module failure, or other system failure
could disrupt remote communications and cause the
outputs to remain active.