Common Module Features
Chapter 3
Multiple Output Point Densities
ControlLogix output modules use either 8-, 16-, or 32-point densities for greater
flexibility in your application. A point is the termination where a wire attaches to
the I/O module from a device. The I/O gets information from the device to this
designated point, thus signaling when activity occurs.
Electronic Fusing
Some digital outputs have internal electronic or mechanical fusing to prevent too
much current from flowing through the module. This feature protects the
module from electrical damage. Other modules require external fusing.
Modules that use electronic fusing are fused on either a per point basis or per
group basis to protect output points from the surge of too much current. If too
much current begins to flow through a point, the fuse is tripped and a point-level
fault is sent to the controller. A corresponding tag can be examined in the event of
a fault. For more information about fault tags, see
.
These modules use electronic fusing:
•
1756-OA8E
•
1756-OB8EI
•
1756-OA8D
•
1756-OB16D
•
1756-OB16E
•
1756-OV16E
•
1756-OV32E
•
1756-OB16IEF
•
1756-OB16IEFS
Refer to
Table 3
to determine what fuse to use in your application. If your module
does not support fusing, you can use a fused IFM to protect outputs. See
publicatio
.
Table 3 - Recommended Fuses
Circuit Type
Cat. No.
Fusing on the module
Recommended Fuse
Fuse Supplier
AC
1756-OA8
(1)
None—Fused IFM can be used to protect outputs
(9)
5x20mm
6.3A Medium lag
SAN-O Industry Corp.
(SOC) p/n
MT 4-6.3A
1756-OA8D
(2)
(3)
Yes—Fused on a per point basis
Electronically fused
1756-OA8E
(2)
(3)
1756-OA16
(1)
(4)
(5)
Yes—Fused on a per group basis
5x20mm
3.15A Slo-Blow
1500A Interruption current
Littelfuse p/n
H2153.15
1756-OA16I
(1)
None—Fused IFM can be used to protect outputs
5x20mm
6.3A Medium lag
SOC p/n
MT 4-6.3A
1756-ON8