Configure ControlLogix Digital I/O Modules
Chapter 7
Connection Properties
Connection properties define controller-to-module behavior. When defining
connection properties, you can do the following:
•
Select a requested packet interval (RPI) to set a defined, maximum period
of time when data is transferred to the owner-controller
•
Choose to inhibit the module
•
Configure the controller so that a loss of connection to this module causes
a major fault
•
View information about the condition of the connection between the
module and the controller
Follow these steps to configure connection properties.
1.
On the Module Properties dialog box, click the Connection tab.
2.
Complete the fields as described below and click OK.
Field
Description
Requested Packet Interval (RPI)
Enter an RPI value or use the default.
See
in Chapter 2 for more information.
Inhibit module
Check the box to prevent communication between the owner-controller and the
module. This option allows for maintenance of the module without faults being
reported to the controller.
See
in Chapter 3 for more information.
Major fault On Controller If
Connection Fails While in Run Mode
Check the box to create a major fault if there is a connection failure with the
module while in Run mode.
For important information on this checkbox, see the Logix5000 Controllers
Information and Status Programming Manual, publicatio
Module Fault
The fault box is empty if you are offline. The type of connection fault appears in
the text box if a fault occurs when the module is online.